Tuesday, 18 September 2012

Oil Level Indicator for transformer


oil level indicator for transformer

Oil Level Indicator for transformer

Magnetic oil level gauge consist of the main body, with following parts-      
 
Gear assembly
Magnetic couple
Float with arm
Cam assembly with mercury switch
Dial with pointer

CONSTRUCTION:
The float is hinged and swings up  or down when oil level rises or falls. This rise or fall rotates the bevel gear and thus the pinion of the gear assembly. The pinion in turns rotates the driving magnet inside the conservator. The follower magnet positioned outside carries a pointer and a cam. The pointer reads oil level and the cam is set to operate the mercury switch at pre determined low level.
Oil level inner side view


Calibration:
The dial is calibrated as per requirement. A drawing showing height of oil level inside the conservator at corresponding marking on dial shall is required.
Alarm switch
One normally open , mercury switch is provided to actuate low level alarm. The switch is adjustable to compensate error in orientation of pad.  Leads of this switch are connected to the terminals.

PARTS LIST
     SR.                DESCRIPTION              MATERIAL
1.                 MAIN BODY             -                   AL (LM6)
2.                LIMIT STOPPERS -                      Brass
3.                LEVER WITH GEAR-                  Brass
4.                FLOAT-ARM-                               Brass
5.                FLOAT                                           Brass
6.                HOLE FOR CABLE GLAND     
7.                CONNECTOR
8.                MERCURY SWITCH GLASS-    Brass
9.                NUT (FOR ADJ. MER. SWITCH)- Brass
10.            DIAL WITH POINTER                AL

   

Typical specification
1.      Operating liquid                      : transformer oil IS 335 or equivalent
2.      Working temperature              : 0-100 deg.c
3.      Working pressure                    : 0-4 kg/cm sq
4.      Environment                           : suitable for indoor and outdoor use
5.      Electrical switch                      : one SPST mercury switch
6.      Contact rating                         : 5 amps 240V, AC. 0.5 amp 240V DC
7.      Switch operation                     : normally open, closes when oil level drops to near  
                                                 empty condition. Switch recovers automatically on  
                                                 rising of oil level.

Sunday, 16 September 2012

Vacuum Circuit Breakers


Vacuum Circuit Breakers (VCB)
                
 In this breaker, vacuum is being used as the arc quenching medium. Vacuum offers highest insulating strength, it has far superior arc quenching properties than any other medium. When contacts of a breaker are opened in vacuum, the interruption occurs at first current zero with dielectric strength between the contacts building up at a rate thousands of times that obtained with other circuit breakers.

   
Principle: When the contacts of the breaker are opened in vacuum (10 -7 to 10 -5 torr), an arc is produced between the contacts by the ionization of metal vapours of contacts. The arc is quickly extinguished because the metallic vapours, electrons, and ions produced during arc condense quickly on the surfaces of the circuit breaker contacts, resulting in quick recovery of dielectric strength. As soon as the arc is produced in vacuum, it is quickly extinguished due to the fast rate of recovery of dielectric strength in vacuum.

 
Construction: It consists of fixed contact, moving contact and arc shield mounted inside a vacuum chamber. The movable member is connected to the control mechanism by stainless steel bellows .This enables the permanent sealing of the vacuum chamber so as to eliminate the possibility of leak .A glass vessel or ceramic vessel is used as the outer insulating body. The arc shield prevents the deterioration of the internal dielectric strength by preventing metallic vapours falling on the inside surface of the outer insulating cover.


 Electrical Maintenance of VCB:

DO’s: Along with PM schedule of Motors
  1. Apply & take clearance from concerned Substation Engineer
  2. Ensure breaker is in Tripped condition, insert the handle in to hole in interlock shaft assembly block & move the handle upward till it comes to FREE position & then pull out Breaker from Service position to Test position.(This is to be done by the concerned S/S operator)
  3. Disengage the Multi-pin plug from the socket.
  4. Rack out the breaker from the cubicle.
  5. Remove the front cover of breaker
  6. Clean the breaker with cotton linen cloth.
  7. Tightness of hardwares to be done
  8. Lubricate the operating mechanism such as Drive lever, coupling rod connected at mechanism shaft, latches, dashpot, opening for manual charging, etc i.e. all sliding & rotational parts.
  9. Charge the closing spring manually for checking free movement of Gear.
  10. Check the plunger of Oil dashpot. Verify that plunger lift up during closing operation & damping action is OK while pressing it down.
  11. Check the trip & closing coil plunger movements are free & the coil casing is properly tightened to frame.
  12. Check ON/OFF indicator, spring charged position indicator is operating correctly.
  13. Check & tighten all the relevant wirings
  14. Measure the resistance of operating coils. If resistance not within +/-5% of the rated value, replace the coil/coils.
  15. Check the contact erosion mark on Vacuum Interrupter, (Bottle). If visible in breaker closed condition, then its OK and if not visible change Vacuum Interrupter.

Parts of VCB
  
(Note: This contact erosion mark is painted either a red line or white dot on the moving stem of vacuum interrupter (lower side)
  1. Check Insulation resistance by 2.5/5KV megger in breaker open condition. (IR>10,000 M-ohms)---This will indicate healthiness of Vacuum Interrupter.
  2. Check motor cut-off switch/aux contacts
  3. Close the spring manually.
  4. Check breaker operation three –four time thru manual closing & tripping.
  5. Fix the front cover.
  6. Insert the breaker in TEST position and electrically charge the spring and check that motor supply is automatically cut off by limit switch.
  7. Check Electrical closing & tripping in test position.
  8. Return LC.
DONT’S:
1.  Do not disturb the various settings marked with red paint.
2.  Do not leave any tools & tackles on the breaker

  
Electrical Operation :
DO’s:
  1. Withdrawal of Breaker from Service to Test position.
A.    Ensure breaker is Tripped condition in service position.
B.     Insert the handle in to hole in interlock shaft assembly block & move the   handle   upward till it comes to FREE position & then pull out Breaker from Service position to Test position.
C.     I it is to be kept in Test position , again insert the handle and move it  downward to its locked position.

  1.  Withdrawal of Breaker out of cubicle from Test position:-
A.    Ensure Plug & socket is disengaged
B.     Interlock is in Locked position
C.     Now, Breaker can be withdrawn
  1. To insert the breaker back into the test position:
A.    Ensure breaker is in Tripped condition
B.     Ensure that interlock is in fully LOCKED position.
C.     Push the breaker till interlock cam is stopped at stop pin of breaker chamber. This is the TEST position of Breaker
  1. To insert the breaker from TEST to Service position:
A.    Ensure breaker is in Tripped condition
B.     Insert the handle & rotate the interlock shaft to FREE position.
C.     Engage the plug & socket
D.    Push the truck further inside till interlock cam is stopped by interlock block
E.     Insert the handle & rotate the interlock shaft to LOCKED position. This will        further push the breaker into its SERVICE position.

NOTE:- Doubly ensure that breaker is to be closed when interlock shaft is in fully LOCKED position. Then only operate the breaker for closing and tripping.

DONT’S:
Don’t operate the breaker unless interlock shaft is in fully LOCKED position. If it is not in fully LOCKED position in SERVICE/TEST position/Outside, while closing the breaker, this will damage the driving/interlocking mechanism ,will disturb the various settings and it can cause single phasing.





Wednesday, 5 September 2012

Earth resistance value

Earth Resistance Value

Earthing network

   

  • Major power station= 0.5 Ohm.
  • Major Sub-stations= 1.0 Ohm
  • Minor Sub-station = 2 Ohm
  • Neutral Bushing. =2 Ohm
  • Service connection = 4 Ohm
  • Medium Voltage Network =2 Ohm
  • L.T.Lightening Arrestor= 4 Ohm
  • L.T.Pole= 5 Ohm
  • H.T.Pole =10 Ohm
  • Tower =20-30 Ohm
Earthing in electrical network – purpose, methods and measurement
The main motto to use earthing is to save man and machine being used in electrical network. . When all metallic parts in electrical equipments are not grounded then if the insulation inside the equipments fails there is the huge rise in voltage level.
If the live wire touches the grounded case then the circuit is effectively shorted and fuse will immediately blow. When the fuse is blown then the dangerous voltages are away.

Purpose of Earthing

 (1)  Safety for Human life/ Building/Equipment

  • To save human life from danger of electrical shock or death by blowing a fuse i.e. To provide an alternative path for the fault current to flow so that it will not endanger the user
  • To protect buildings, machinery & appliances under fault conditions.
  • To ensure that all exposed conductive parts do not reach a dangerous potential.
  • To provide safe path to dissipate lightning and short circuit currents.
  • To provide stable platform for operation of sensitive  electronic equipments   i.e. To maintain the voltage at any part of an electrical system at a known value so as to prevent over current or excessive voltage on the appliances or equipment .

(2)  Over voltage protection

Lightning, line surges or unintentional contact with higher voltage lines can cause dangerously high voltages to the electrical distribution system. Earthing provides an alternative path around the electrical system to minimize damages in the System.

(3)  Voltage stabilization

There are many sources of electricity. Every transformer can be considered a separate source. If there were not a common reference point for all these voltage sources it would be extremely difficult to calculate their relationships to each other.
The earth is the most omnipresent conductive surface, and so it was adopted in the very beginnings of electrical distribution systems as a nearly universal standard for all electric systems.

Conventional methods of earthing

(1)  Plate type Earthing

  • Generally for plate type earthing normal Practice is to use
  • Cast iron plate of size 600 mm x600 mm x12 mm. OR
  • Galvanized iron plate of size 600 mm x600 mm x6 mm. OR
  • Copper plate of size 600 mm * 600 mm * 3.15 mm
  • Plate  burred at the depth of 8 feet in the vertical position and GI strip of size 50 mmx6 mm bolted with the plate is brought up to the ground level.
  • These types of earth pit are generally filled with alternate layer of charcoal & salt up to 4 feet from the bottom of the pit.

(2)  Pipe type Earthing

For Pipe type earthing normal practice is to use GI pipe [C-class] of 75 mm diameter, 10 feet long welded with 75 mm diameter GI flange having 6 numbers of holes for the connection of earth wires and inserted in ground by auger method. These types of earth pit are generally filled with alternate layer of charcoal & salt or earth reactivation compound.

Method for Construction of Earthing Pit

  • Excavation on earth for a normal earth Pit size is 1.5M X 1.5M X 3.0 M.
  • Use 500 mm X 500 mm X 10 mm GI Plate or Bigger Size for more Contact of Earth and reduce Earth Resistance.
  • Make a mixture of Wood Coal Powder Salt & Sand all in equal part
  • Wood Coal Powder use as good conductor of electricity, anti corrosive, rust proves for GI Plate for long life.
  • The purpose of coal and salt is to keep wet the soil permanently.
  • The salt percolates and coal absorbs water keeping the soil wet.
  • Care should always be taken by watering the earth pits in summer so that the pit soil will be wet.
  • Coal is made of carbon which is good conductor minimizing the earth resistant.
  • Salt use as electrolyte to form conductivity between GI Plate Coal and Earth with humidity.
  • Sand has used to form porosity to cycle water & humidity around the mixture.
  • Put GI Plate (EARTH PLATE) of size 500 mm X 500 mm X 10 mm in the mid of mixture.
  • Use Double GI Strip size 30 mm X 10 mm to connect GI Plate to System Earthling.
  • It will be better to use GI Pipe of size 2.5″ diameter with a Flange on the top of GI Pipe to cover GI Strip from EARTH PLATE to Top Flange.
  • Cover Top of GI pipe with a T joint to avoid jamming of pipe with dust & mud and also use water time to time through this pipe to bottom of earth plate.
  • Maintain less than one Ohm Resistance from EARTH PIT conductor to a distance of 15 Meters around the EARTH PIT with another conductor dip on the Earth at least 500 mm deep.
  • Check Voltage between Earth Pit conductors to Neutral of Mains Supply 220V AC 50 Hz it should be less than 2.0 Volts.

Factors affecting on Earth resistivity

(1)  Soil Resistivity

It is the resistance of soil to the passage of electric current. The earth resistance value (ohmic value) of an earth pit depends on soil resistivity. It is the resistance of the soil to the passage of electric current.
It varies from soil to soil. It depends on the physical composition of the soil, moisture, dissolved salts, grain size and distribution, seasonal variation, current magnitude etc. In depends on the composition of soil, Moisture content, Dissolved salts, grain size and its distribution, seasonal variation, current magnitude.

(2)  Soil Condition

Different soil conditions give different soil resistivity. Most of the soils are very poor conductors of electricity when they are completely dry. Soil resistivity is measured in ohm-meters or ohm-cm.
Soil plays a significant role in determining the performance of Electrode. Soil with low resistivity is highly corrosive. If soil is dry then soil resistivity value will be very high.
If soil resistivity is high, earth resistance of electrode will also be high.

(3)  Moisture

Moisture has a great influence on resistivity value of soil. The resistivity of a soil can be determined by the quantity of water held by the soil and resistivity of the water itself. Conduction of electricity in soil is through water.
The resistance drops quickly to a more or less steady minimum value of about 15% moisture. And further increase of moisture level in soil will have little effect on soil resistivity. In many locations water table goes down in dry weather conditions. Therefore, it is essential to pour water in and around the earth pit to maintain moisture in dry weather conditions. Moisture significantly influences soil resistivity

(4)  Dissolved salts

Pure water is poor conductor of electricity. Resistivity of soil depends on resistivity of water which in turn depends on the amount and nature of salts dissolved in it.
Small quantity of salts in water reduces soil resistivity by 80%. common salt is most effective in improving conductivity of soil. But it corrodes metal and hence discouraged.

(5)  Climate Condition

Increase or decrease of moisture content determines the increase or decrease of soil resistivity.
Thus in dry whether resistivity will be very high and in monsoon months the resistivity will be low.

(6)  Physical Composition

Different soil composition gives different average resistivity. Based on the type of soil, the resistivity of clay soil may be in the range of 4 – 150 ohm-meter, whereas for rocky or gravel soils, the same may be well above 1000 ohm-meter.

(7)  Location of Earth Pit

The location also contributes to resistivity to a great extent. In a sloping landscape, or in a land with made up of soil, or areas which are hilly, rocky or sandy, water runs off and in dry weather conditions water table goes down very fast. In such situation Back fill Compound will not be able to attract moisture, as the soil around the pit would be dry.
The earth pits located in such areas must be watered at frequent intervals, particularly during dry weather conditions.
Though back fill compound retains moisture under normal conditions, it gives off moisture during dry weather to the dry soil around the electrode, and in the process loses moisture over a period of time. Therefore, choose a site that is naturally not well drained.

(8)  Effect of grain size and its distribution

Grain size, its distribution and closeness of packing are also contributory factors, since they control the manner in which the moisture is held in the soil.
Effect of seasonal variation on soil resistivity: Increase or decrease of moisture content in soil determines decrease or increase of soil resistivity. Thus in dry weather resistivity will be very high and during rainy season the resistivity will be low.

(9)  Effect of current magnitude

Soil resistivity in the vicinity of ground electrode may be affected by current flowing from the electrode into the surrounding soil.
The thermal characteristics and the moisture content of the soil will determine if a current of a given magnitude and duration will cause significant drying and thus increase the effect of soil resistivity

(10) Area Available

Single electrode rod or strip or plate will not achieve the desired resistance alone.
If a number of electrodes could be installed and interconnected the desired resistance could be achieved. The distance between the electrodes must be equal to the driven depth to avoid overlapping of area of influence. Each electrode, therefore, must be outside the resistance area of the other.

(11)  Obstructions

The soil may look good on the surface but there may be obstructions below a few feet like virgin rock. In that event resistivity will be affected. Obstructions like concrete structure near about the pits will affect resistivity.
If the earth pits are close by, the resistance value will be high.

(12)    Current Magnitude

A current of significant magnitude and duration will cause significant drying condition in soil and thus increase the soil resistivity.

Measurement of Earth Resistance by use of Earth Tester

  • For measuring soil resistivity Earth Tester is used. It is also called the “MEGGER”.
  • It has a voltage source, a meter to measure Resistance in ohms, switches to change instrument range, Wires to connect terminal to Earth Electrode and Spikes.
  • It is measured by using Four Terminal Earth Tester Instrument. The terminals are connected by wires as in illustration.
  • P=Potential Spike and C=Current Spike. The distance between the spikes may be 1M, 2M, 5M, 10M, 35M, and 50M.
  • All spikes are equidistant and in straight line to maintain electrical continuity.  Take measurement in different directions.
  • Soil resistivity =2πLR.
  • R= Value of Earth resistance in ohm.
  • Distance between the spikes in cm.
  • π  =  3.14
  • P = Earth resistivity ohm-cm.
  • Earth resistance value is directly proportional to Soil resistivity value


                Three point method



 Measurement of Earth Resistance (Three point method)

In this method earth tester terminal C1 & P1 are shorted to each other and connected to the earth electrode (pipe) under test. Terminals P2 & C2 are connected to the two separate spikes driven in earth.  These two spikes are kept in same line at the distance of 25 meters and 50 meters due to which there will not be mutual interference in the field of individual spikes.
If we rotate generator handle with specific speed we get directly earth resistance on scale. Spike length in the earth should not be more than 1/20th distance between two spikes. Resistance must be verified by increasing or decreasing the distance between the tester electrode and the spikes by 5 meter. Normally, the length of wires should be 10 and 15 Meter or in proportion of 62% of ‘D’.
Suppose, the distance of Current Spike from Earth Electrode D = 60 ft, Then, distance of Potential Spike would be 62 % of D = 0.62D i.e.  0.62 x 60 ft = 37 ft.

Four Point Method

In this method 4 spikes are driven in earth in same line at the equal distance.  Outer two spikes are connected to C1 & C2 terminals of earth tester.  Similarly inner two spikes are connected to P1 & P2 terminals.  Now if we rotate generator handle with specific speed, we get earth resistance value of that place.
In this method error due to polarization effect is eliminated and earth tester can be operated directly on A.C.

GI Earthing Vs Copper Earthing

  • As per IS 3043, the resistance of Plate electrode to earth (R) = (r/A) X under root(P/A).
  • Where r = Resistivity of Soil Ohm-meter.
  • A=Area of Earthing Plate m3.
  • The resistance of Pipe electrode to earth (R) = (100r/2πL) X loge (4L/d).
  • Where L= Length of Pipe/Rod in cm
  • d=Diameter of Pipe/Rod in cm.
  • The resistivity of the soil and the physical dimensions of the electrode play important role of resistance of Rod with earth.
  • The material resistivity is not considered important role in earth resistivity.
  • Any material of given dimensions would offer the same resistance to earth. Except the sizing and number of the earthing conductor or the protective conductor.

Pipe Earthing Vs Plate Earthing

  • Suppose Copper Plate having of size 1.2m x 1.2m x 3.15mm thick. soil resistivity of 100 ohm-m,
  • The resistance of Plate electrode to earth (R)=( r/A)X under root(π/A) = (100/2.88)X(3.14/2.88)=36.27 ohm
  • Now, consider a GI Pipe Electrode of 50 mm Diameter and 3 m Long. soil resistivity of 100 Ohm-m,
  • The resistance of Pipe electrode to earth (R) = (100r/2πL) X loge (4L/d) = (100X100/2X3.14X300) X loge (4X300/5) =29.09 Ohm.
  • From the above calculation the GI Pipe electrode offers a much lesser resistance than even a copper plate electrode.
  • As per IS 3043 Pipe, rod or strip has a much lower resistance than a plate of equal surface area.

Length of Pipe Electrode and Earthing Pit

 The resistance to earth of a pipe or plate electrode reduces rapidly within the first few feet from ground (mostly 2 to 3 meter) but after that soil resistivity is mostly uniform.
After about 4 meter depth, there is no appreciable change in resistance to earth of the electrode. Except a number of rods in parallel are to be preferred to a single long rod.

Amount of Salt and Charcoal (more than 8Kg)

 To reduce soil resistivity, it is necessary to dissolve in the moisture particle in the Soil. Some substance like Salt/Charcoal is highly conductive in water solution but the additive substance would reduce the resistivity of the soil, only when it is dissolved in the moisture in the soil after that additional quantity does not serve the Purpose.
5% moisture in Salt reduces earth resistivity rapidly and further increase in salt content will give a very little decrease in soil resistivity.
The salt content is expressed in percent by weight of the moisture content in the soil. Considering 1M3 of Soil, the moisture content at 10 percent will be about 144 kg. (10 percent of 1440 kg). The salt content shall be 5% of this (i.e.) 5% of 144kg, that is, about 7.2kg.

Amount of Water Purring

Moisture content is one of the controlling factors of earth resistivity. Above 20 % of moisture content, the resistivity is very little affected. But below 20% the resistivity increases rapidly with the decrease in moisture content.
If the moisture content is already above 20% there is no point in adding quantity of water into the earth pit, except perhaps wasting an important and scarce national resource like water.

Length Vs Diameter of Earth Electrode

Apart from considerations of mechanical strength, there is little advantage to be gained from increasing the earth electrode diameter with the object in mind of increasing surface area in contact with the soil.
The usual practice is to select a diameter of earth electrode, which will have enough strength to enable it to be driven into the particular soil conditions without bending or splitting. Large diameter electrode may be more difficult to drive than smaller diameter electrode.
The depth to which an earth electrode is driven has much more influence on its electrical resistance characteristics than has its diameter.
Treatments to for minimizing Earth resistance
  • Remove Oxidation on joints and joints should be tightened.
  • Poured sufficient water in earth electrode.
  • Used bigger size of Earth Electrode.
  • Electrodes should be connected in parallel.
  • Earth pit of more depth & width- breadth should be made.