Friday 2 August 2013

Electrical thumb rule

Cable current Capacity:
  • For Copper  Wire Current Capacity (Up to 25 Sq.mm) = 5-6X Size of Wire in Sq.mm
  • Ex. For 4 Sq.mm=6×4=24 Amp, 
  • For Aluminum wire Current Capacity = 4X Size of Cable in Sq.mm ,upto 10sqmm
  • Ex. For 1.5 Sq.mm=4×1.5=6 Amp.
Nomenclature for cable Rating 
Uo=Phase-Ground Voltage, U=Phase-Phase Voltage, Um=Highest Permissible Voltage
Current Capacity of Equipments:
  • 1 Phase Motor draws Current=6-7Amp per HP.
  • 3 Phase Motor draws Current=1.7Amp per KW.
  • Full Load Current of 3 Phase Motor=HPx1.3 from 10 HP onward
  • Full Load Current of 1 Phase Motor=5 to 6 times of HP
  • No Load Current of 3 Phase Motor =25-30% of FLC
  • KW Rating of Motor=HPx0.75
  • Full Load Current of equipment =1.39xKVA (for 3 Phase 415Volt)
  • Full Load Current of equipment =1.74xKw (for 3 Phase 415Volt)
Earthing Resistance:
  • Earthing Resistance for Single Pit=5Ω ,
  • Earthing Grid=0.5Ω
  • As per NEC 1985 Earthing Resistance should be <5Ω.
  • Voltage between Neutral and Earth <=2 Volts
  • Resistance between Neutral and Earth <=1Ω
  • Creepage Distance=18 to 22mm/KV (Moderate Polluted Air) or
  • Creepage Distance=25 to 33mm/KV (Highly Polluted Air)

Insulation Resistance:
  • IR Value for Rotating Machine= (KV+1) MΩ.
  • IR Value for Motor (IS 732) = ((20xVoltage (L-L)) / (1000+ (2xKW)).
  • IR Value for Equipment (<1KV) = Minimum 1 MΩ.
  • IR Value for Equipment (>1KV) = KV 1 MΩ per 1KV.
  • IR Value for Panel = 2 x KV rating of the panel.
  • Min Insulation Resistance Value (Domestic) = 50 MΩ / No of Points. (All Electrical Points with Electrical fitting & Plugs). Should be less than 0.5 MΩ
  • Min Insulation Resistance Value (Commercial) = 100 MΩ / No of Points. (All Electrical Points without fitting & Plugs).Should be less than 0.5 MΩ.
  • Test Voltage (A.C) for Meggering = (2X Name Plate Voltage) +1000
  • Test Voltage (D.C) for Meggering = (2X Name Plate Voltage).
  • Submersible Pump Take 0.4 KWH of extra Energy at 1 meter drop of Water.
Lighting Arrestor:
  • Arrestor have Two Rating=
  • (1) MCOV=Max. Continuous Line to Ground Operating Voltage.
  • (2) Duty Cycle Voltage. (Duty Cycle Voltage>MCOV).
Transformer:
  • Current Rating of Transformer=KVAx1.35
  • Short Circuit Current of Generator/transformer
= Current Rating / % Impedance

  • No Load Current of Transformer=<2% of Transformer Rated current
  • Capacitor Current (Ic)=KVAR / 1.732xVolt (Phase-Phase)
  • Typically the local utility provides transformers rated up to 500kVA For maximum connected load of 99kW,
  • Typically the local utility provides transformers rated up to 1250kVA For maximum connected load of 150kW.
  • The diversity they would apply to apartments is around 60%
  • Maximum HT (11kV) connected load will be around 4.5MVA per circuit.
  • 4No. earth pits per transformer (2No. for body and 2No. for neutral earthing),
  • Clearances, approx.1000mm around Transformer allow for transformer movement for replacement. 
Diesel Generator:
  • Diesel Generator Set Produces=3.87 Units (KWH) in 1 Litter of Diesel.
  • Requirement Area of Diesel Generator = for 25KW to 48KW=56 Sq.meter, 100KW=65 Sq.meter.
  • DG less than or equal to 1000kVA must be in a canopy.
  • DG greater 1000kVA can either be in a canopy or skid mounted in an acoustically treated room
  • DG noise levels to be less than 75dBA @ 1meter.
  • DG fuel storage tanks should be a maximum of 990 Litter per unit Storage tanks above this level will trigger more stringent explosion protection provision.
Current Transformer:
Nomenclature of CT:
  • Ratio: input / output current ratio
  • Burden (VA): total burden including pilot wires. (2.5, 5, 10, 15 and 30VA.)
  • Class: Accuracy required for operation (Metering: 0.2, 0.5, 1 or 3, Protection: 5, 10, 15, 20, 30).
  • Accuracy Limit Factor:
  • Nomenclature of CT: Ratio, VA Burden, Accuracy Class, Accuracy Limit Factor.Example: 1600/5, 15VA 5P10  (Ratio: 1600/5, Burden: 15VA, Accuracy Class: 5P, ALF: 10)
  • As per IEEE Metering CT: 0.3B0.1 rated Metering CT is accu­rate to 0.3 percent if the connected secondary burden if imped­ance does not exceed 0.1 ohms.
  • As per IEEE Relaying (Protection) CT: 2.5C100 Relaying CT is accurate within 2.5 percent if the secondary burden is less than 1.0 ohm (100 volts/100A).


2 comments:

  1. Totally Copy paste from www.electricalnotes.wordpress.com

    ReplyDelete

One Nation, One electrical License

Electrical contractors are facing license problem when they bid for another state. Generally they are entitled to do work in particular stat...