Copper and iron weight or content in Transformer


TRANSFORMER 11/0.415 KV
Sr
TR KVA
Un tanking Mass (core+ winding), KG
Oil Mass, KG
Total mass (oil core+ coil +tank +c conservator), KG
Iron Content
Copper Content
Insulation Waste
1
25
110
66
274
85.25
13.75
11
2
63
240
148
508
186.00
30.00
24
3
100
255
189
605
197.63
31.88
25.5
4
200
350
290
800
271.25
43.75
35
5
300
1760
1100
3560
1364
220
176
6
500
860
550
2105
666.5
107.5
86
7
800
1000
650
2500
775
125
100
8
1000
1280
700
3200
992
160
128
9
1400
3010
1100
4700
2332.75
376.25
301
10
2000
2600
950
4900
2015
325
260
11
2500
3700
1430
7320
2867.5
462.5
370
12
3500
4000
2200
10000
3100
500
400

Transformer 33/0.4/11 KV
Sr
TR KVA
Un tanking Mass (core+ winding), KG
Oil Mass, KG
Total mass (oil core+ coil +tank +c conservator), KG
Iron Content
Copper Content
Insulation Waste
1
100
220
165
550
170.5
27.5
22
2
200
460
247
945
356.5
57.5
46
3
500
760
500
1900
589.00
95.00
76
4
1000
1340
750
3350
1038.5
167.5
134
5
2000
2320
1450
5800
1798
290
232
6
2500
2640
1750
6600
2046
330
264
7
10000
10000
4050
20000
7750
1250
1000
8
25000
29760
9750
49683
23064
3720
2976
Note: the above data is based for empirical formula so reader should verify name plate or manufacturer.
Generic formula:
Sr.   Type of Metal                                                 % of mass ( metal content)
1.       Total mass of ferrous material (iron)                             77.5 % of untanking mass
2.       Total Mass of Copper(Coil)                                            12.5 % of untanking mass
3.       Total Mass of insulation                                                 10 % of the untanking mass

Commissioning of machinery or project