Earthing strip matrix for transformer


Earthing strip size for transformer.
Cross Section Area of Earthing Conductor As per IS 3043
A = (If x√t) / K  
Where:
t = Fault current Time (Second)., 1 sec or 3 sec
K = Material Constant, Material Constant, For GI=80, copper K=206, Aluminium K=126).
Part-A: Typical Protective conductor size required for Transformer Ratings (100-500KVA)





Sr.
A
B
C
D
E
F
1
Transformer Rating ( KVA)
100
160
250
315
500
2
Secondary Voltage (V)
433
433
433
433
433
3
Full Load current
133
213
333
420
667
4
Percentage Impedance Z%
5
5
5
5
5
5
Short Circuit Current (SC) in A =FLC*(100/Impedance)
2660
4260
6600
8400
13340
6
Area of Protective conductor Reqd in sq.mm = SC *√t/k





7
t = 1 Sec





8
Copper k = 206
12.9
20.7
32.0
40.8
64.8
9
Recommended strip size
25 x 3 mm
25 x 3 mm
25 x 3 mm
25 x 3 mm
25 x 3 mm
10
Alluminium k = 126
21.1
33.8
52.4
66.67
105.9
11
Recommended strip size
25 x 3 mm
25 x 3 mm
25 x 3 mm
25 x 3 mm
25 x 6 mm
12
Steel, k= 80
33.3
53.3
82.5
105
166.8
13
Recommended strip size
25 x 3 mm
25 x 3 mm
25 x 6 mm
25 x 6 mm
40 x 6 mm
14
t =3 Sec





15
Copper k = 206
22.34
35.85
56.42
70.67
112.23
16
Recommended strip size
25 x 3 mm
25 x 3 mm
25 x 3 mm
25 x 3 mm
25 x 6 mm
17
Alluminium k = 126
36.55
58.54
90.76
115.47
183.42
18
Recommended strip size
25 x 3 mm
25 x 3 mm
25 x 6 mm
25 x 6 mm
40 x 6 mm
19
Steel , k= 80
57.68
92.32
142.89
181.86
288.9
20
Recommended strip size
25 x 3 mm
25 x 6 mm
25 x 6 mm
40 x 6 mm
50 x 6 mm

PART-B: Typical Protective conductor size required for Transformer Ratings (630-2000KVA)
Sr.
A
G
H
I
J
K
L
1
Transformer Rating ( KVA)
630
750
1000
1250
1600
2000
2
Secondary Voltage (V)
433
433
433
433
433
433
3
Full Load current
840
1000
1333
1667
2133
2667
4
Percentage Impedance Z%
5
5
5
6
6
6
5
Short Circuit Current (SC) in A
16801
20001
26668
27779
35558
44447
6
Area of Protective conductor Reqd in sq.mm = SC *√t/k






7
t = 1Sec






8
Copper k = 206
81.96
97.57
130.09
135.51
173.45
216.81
9
Recommended strip size
25 x 6 mm
25 x 6 mm
25 x 6 mm
25 x 6 mm
40 x 6 mm
40 x 6 mm
10
Alluminium k = 126
133.34
158.74
211.65
220.47
282.2
352.75
11
Recommended strip size
25 x 6 mm
40 x 6 mm
40 x 6 mm
40 x 6 mm
50 x 6 mm
75 x 6 mm
12
Steel, k= 80
210.01
250.01
333.35
347.24
444.47
555.59
13
Recommended strip size
40 x 6 mm
50 x 6 mm
75 x 6 mm
75 x 6 mm
75 x 6 mm
75 x10 mm
14
t =3 Sec






15
Copper k = 206
141.26
168.17
224.22
233.56
298.96
373.7
16
Recommended strip size
25 x 6 mm
40 x 6 mm
40 x 6 mm
40 x 6 mm
50 x 6 mm
75 x 6 mm
17
Alluminium k = 126
230.95
274.94
366.58
381.86
488.78
610.97
18
Recommended strip size
40 x 6 mm
50 x 6 mm
75 x 6 mm
75 x 6 mm
75 x 10 mm
75 x 10 mm
19
Steel , k= 80
363.74
433.03
577.37
601.42
769.82
962.28
20
Recommended strip size
75 x 6 mm
75 x 6 mm
75 x10 mm
75 x10 mm
100 x 10 mm
100 x 10 mm


Reader can choose safely factor as 1.5.
Suppose calculated strip size is 40x6 sqmm = 240sqmm
Considering safety factor , strip size = 240x1.5 = 360 sqmm.
Electrode always should be installed in 2 and opposte side of equipment. The distance between electrode is not less than height of one electrode.