Earthing strip size for
transformer.
Cross Section Area of Earthing Conductor As per IS
3043
A = (If x√t) / K
Where:
t
= Fault current Time (Second)., 1 sec or 3 sec
K
= Material Constant, Material Constant, For GI=80, copper K=206, Aluminium
K=126).
Part-A:
Typical Protective conductor size required for Transformer Ratings
(100-500KVA)
|
|
|
|
|
||
Sr.
|
A
|
B
|
C
|
D
|
E
|
F
|
1
|
Transformer Rating ( KVA)
|
100
|
160
|
250
|
315
|
500
|
2
|
Secondary Voltage (V)
|
433
|
433
|
433
|
433
|
433
|
3
|
Full Load current
|
133
|
213
|
333
|
420
|
667
|
4
|
Percentage Impedance Z%
|
5
|
5
|
5
|
5
|
5
|
5
|
Short Circuit Current (SC) in A =FLC*(100/Impedance)
|
2660
|
4260
|
6600
|
8400
|
13340
|
6
|
Area of Protective conductor Reqd in sq.mm = SC *√t/k
|
|
|
|
|
|
7
|
t = 1 Sec
|
|
|
|
|
|
8
|
Copper k = 206
|
12.9
|
20.7
|
32.0
|
40.8
|
64.8
|
9
|
Recommended strip size
|
25 x 3 mm
|
25 x 3 mm
|
25 x 3 mm
|
25 x 3 mm
|
25 x 3 mm
|
10
|
Alluminium k = 126
|
21.1
|
33.8
|
52.4
|
66.67
|
105.9
|
11
|
Recommended strip size
|
25 x 3 mm
|
25 x 3 mm
|
25 x 3 mm
|
25 x 3 mm
|
25 x 6 mm
|
12
|
Steel, k= 80
|
33.3
|
53.3
|
82.5
|
105
|
166.8
|
13
|
Recommended strip size
|
25 x 3 mm
|
25 x 3 mm
|
25 x 6 mm
|
25 x 6 mm
|
40 x 6 mm
|
14
|
t =3 Sec
|
|
|
|
|
|
15
|
Copper k = 206
|
22.34
|
35.85
|
56.42
|
70.67
|
112.23
|
16
|
Recommended strip size
|
25 x 3 mm
|
25 x 3 mm
|
25 x 3 mm
|
25 x 3 mm
|
25 x 6 mm
|
17
|
Alluminium k = 126
|
36.55
|
58.54
|
90.76
|
115.47
|
183.42
|
18
|
Recommended strip size
|
25 x 3 mm
|
25 x 3 mm
|
25 x 6 mm
|
25 x 6 mm
|
40 x 6 mm
|
19
|
Steel , k= 80
|
57.68
|
92.32
|
142.89
|
181.86
|
288.9
|
20
|
Recommended strip size
|
25 x 3 mm
|
25 x 6 mm
|
25 x 6 mm
|
40 x 6 mm
|
50 x 6 mm
|
PART-B:
Typical Protective conductor size required for Transformer Ratings
(630-2000KVA)
Sr.
|
A
|
G
|
H
|
I
|
J
|
K
|
L
|
1
|
Transformer Rating ( KVA)
|
630
|
750
|
1000
|
1250
|
1600
|
2000
|
2
|
Secondary Voltage (V)
|
433
|
433
|
433
|
433
|
433
|
433
|
3
|
Full Load current
|
840
|
1000
|
1333
|
1667
|
2133
|
2667
|
4
|
Percentage Impedance Z%
|
5
|
5
|
5
|
6
|
6
|
6
|
5
|
Short Circuit Current (SC) in A
|
16801
|
20001
|
26668
|
27779
|
35558
|
44447
|
6
|
Area of Protective conductor Reqd in sq.mm = SC *√t/k
|
|
|
|
|
|
|
7
|
t = 1Sec
|
|
|
|
|
|
|
8
|
Copper k = 206
|
81.96
|
97.57
|
130.09
|
135.51
|
173.45
|
216.81
|
9
|
Recommended strip size
|
25 x 6 mm
|
25 x 6 mm
|
25 x 6 mm
|
25 x 6 mm
|
40 x 6 mm
|
40 x 6 mm
|
10
|
Alluminium k = 126
|
133.34
|
158.74
|
211.65
|
220.47
|
282.2
|
352.75
|
11
|
Recommended strip size
|
25 x 6 mm
|
40 x 6 mm
|
40 x 6 mm
|
40 x 6 mm
|
50 x 6 mm
|
75 x 6 mm
|
12
|
Steel, k= 80
|
210.01
|
250.01
|
333.35
|
347.24
|
444.47
|
555.59
|
13
|
Recommended strip size
|
40 x 6 mm
|
50 x 6 mm
|
75 x 6 mm
|
75 x 6 mm
|
75 x 6 mm
|
75 x10 mm
|
14
|
t =3 Sec
|
|
|
|
|
|
|
15
|
Copper k = 206
|
141.26
|
168.17
|
224.22
|
233.56
|
298.96
|
373.7
|
16
|
Recommended strip size
|
25 x 6 mm
|
40 x 6 mm
|
40 x 6 mm
|
40 x 6 mm
|
50 x 6 mm
|
75 x 6 mm
|
17
|
Alluminium k = 126
|
230.95
|
274.94
|
366.58
|
381.86
|
488.78
|
610.97
|
18
|
Recommended strip size
|
40 x 6 mm
|
50 x 6 mm
|
75 x 6 mm
|
75 x 6 mm
|
75 x 10 mm
|
75 x 10 mm
|
19
|
Steel , k= 80
|
363.74
|
433.03
|
577.37
|
601.42
|
769.82
|
962.28
|
20
|
Recommended strip size
|
75 x 6 mm
|
75 x 6 mm
|
75 x10 mm
|
75 x10 mm
|
100 x 10 mm
|
100 x 10 mm
|
Reader
can choose safely factor as 1.5.
Suppose
calculated strip size is 40x6 sqmm = 240sqmm
Considering
safety factor , strip size = 240x1.5 = 360 sqmm.
Electrode
always should be installed in 2 and opposte side of equipment. The distance
between electrode is not less than height of one electrode.
No es un secreto que tengo una relación muy profunda y personal con Dios. He presionado y resistido a esa relación el año pasado a través de toda la mierda que tuve que pasar por vivir con Herpes, pero una vez más, Dios es más grande que mi terquedad y rompió ese brote de herpes labial y todo lo que tenía era Herpes Genital. Para mí personalmente, escuchar una y otra vez que no soy lo suficientemente bueno realmente ha invadido mi mente de la peor manera posible. Me apagué por completo y me estaba despertando, así es como la vida va a terminar con este brote temporal de herpes "jodan a todos con herpes si saben a qué me refiero", pero seamos honestos aquí ... Es un cobarde decirle que no a medicina herbaria. Se basa en el miedo. Y es deshonesto a lo que mi corazón quiere. No construyas un muro a tu alrededor porque tienes miedo de los herbarios o de dar un paso audaz, especialmente cuando se trata de problemas de salud y de curación. Muchos hombres y mujeres jóvenes me dicen una y otra vez que el Dr. Itua me va a estafar, pero hoy le doy una oportunidad. Creo que nadie me va a convencer de la medicina herbal. Acepto la medicina herbal del Dr. Itua porque cura mi herpes. solo dos semanas de beberlo y he estado viviendo durante un año y meses. Ya no tengo más brotes. Puede contactarlo si necesita su medicina herbal para enfermedades como el VIH, la epilepsia, la infertilidad, el herpes, la hepatitis, la esquizofrenia. Cáncer, Fibromialgia, Fibrodisplasia de Fluoroquinolona Ossificans Progressiva.Dupuytren, Desmoplastic, Diabetes, Celia, Angiopatía Amiloide Cerebral, HPV, Erección Débil, Removedor de Verrugas. Ataxia, artritis, esclerosis lateral amiotrófica, enfermedad de Alzheimer, carcinoma adrenocortical. Asma alérgica, hechizo de amor. Email..drituaherbalcenter @ gmail.com y luego qué es la aplicación. + 2348149277967 .... Mi consejo para cualquier hombre / mujer enfermo es simple ... Sea siempre un libro abierto. Sé muy sincero acerca de ti mismo, de tu situación y de lo que eres. No retengas nada. Retenerte no te llevará a ningún lado ... tal vez un boleto de ida a Lonelyville y ese NO sea un lugar donde quieras estar. Así que mi verdad final ... y estoy empezando a entender esto ...