Voltage drop calculation, Cable size
and resistance
An approximate
check can be made on voltage drop by means of the following formulae-
For DC and single phase AC two
wire systems
Voltage drop = (2xIxLxRxt)/1000
Where  I = current in ampere 
L = length of cable
in meter 9one conductor only)
R = resistance of
one conductor from table 
t = temperature
correction factor 
For three phase AC systems
Voltage drop = (1.732xIxLxRxt)/1000
Note: formula is applied when
power factor is unity. Power factor to be considered in load and reactance to
be considered.
i).Cable size and resistance 
| 
Cross sectional
  area in sqmm. | 
Sq. inch  | 
Copper | 
Aluminium | ||
| 
Weight  kg/km | 
Resistance at 20 deg.C , ohm/km | 
Weight  kg/km | 
Resistance at 20 deg.C , ohm/km | ||
| 
1 | 
0.00155 | 
8.89 | 
17.86 | 
2.7 | 
30.3 | 
| 
1.5 | 
0.00230 | 
13.34 | 
11.91 | 
4.04 | 
20.2 | 
| 
2.5 | 
0.0038 | 
22.33 | 
7.1444 | 
6.74 | 
12.12 | 
| 
4 | 
0.0062 | 
35.56 | 
4.46 | 
10.8 | 
7.575 | 
| 
6 | 
0.0093 | 
53.34 | 
2.977 | 
16.2 | 
5.05 | 
| 
10 | 
0.0155 | 
88.9 | 
1.786 | 
27 | 
3.03 | 
| 
16 | 
0.0248 | 
142.2 | 
1.116 | 
43.2 | 
1.894 | 
| 
25 | 
0.0388 | 
222.3 | 
0.714 | 
67.4 | 
1.212 | 
| 
35 | 
0.0543 | 
311.2 | 
0.510 | 
94.4 | 
0.866 | 
| 
50 | 
0.078 | 
444.5 | 
0.357 | 
135 | 
0.608 | 
| 
70 | 
0.108 | 
622.3 | 
0.255 | 
189 | 
0.433 | 
| 
95 | 
0.147 | 
844.6 | 
0.188 | 
256 | 
0.319 | 
| 
120 | 
0.186 | 
1067 | 
0.1488 | 
323 | 
0.2525 | 
| 
150 | 
0.233 | 
1334 | 
0.1191 | 
404 | 
0.202 | 
| 
185 | 
0.286 | 
1645 | 
0.0965 | 
498 | 
0.1638 | 
| 
240 | 
0.372 | 
2134 | 
0.0744 | 
646 | 
0.1263 | 
| 
300 | 
0.465 | 
2677 | 
0.0595 | 
808 | 
0.101 | 
| 
400 | 
0.620 | 
3556 | 
0.0447 | 
1016 | 
0.0758 | 
| 
500 | 
0.780 | 
4445 | 
0.0357 | 
1356 | 
0.0606 | 
| 
625 | 
0.956 | 
5556 | 
0.0286 | 
1688 | 
0.0485 | 
For building
wires and flex cord, add 5% more
ii) Resistance correction factor at different temperature
ii) Resistance correction factor at different temperature
| 
Temperature in
  deg.C | 
Temperature
  Correction Factor  | |
| 
Copper  | 
Aluminium  | |
| 
5 | 
0.9411 | 
0.9396 | 
| 
10 | 
0.9607 | 
0.9597 | 
| 
15 | 
0.9804 | 
0.9798 | 
| 
20 | 
1.0000 | 
1.000 | 
| 
25 | 
1.0197 | 
1.0202 | 
| 
30 | 
1.0392 | 
1.0403 | 
| 
35 | 
1.0589 | 
1.0604 | 
| 
40 | 
1.0786 | 
1.0806 | 
| 
45 | 
1.0982 | 
1.1008 | 
| 
50 | 
1.1179 | 
1.1209 | 
| 
55 | 
1.1375 | 
1.1410 | 
| 
60 | 
1.1572 | 
1.1610 | 
| 
65 | 
1.1768 | 
1.1814 | 
| 
70 | 
1.1965 | 
1.2015 | 
| 
75 | 
1.2161 | 
1.2216 | 
| 
80 | 
1.2358 | 
1.2418 | 
Book
reference: a practical guide to cable installation and toolbox talk
In India-
DISCOVERY PUBLISHING HOUSE PVT. LTD
4383/4B, Ansari Road, Darya Ganj
New Delhi–110002 (India)
Tel: +91-11-23279245 / 43596064 / 43596065
Fax.: +91-11-23253475
E-mail: discoverypublishinghouse@gmail.com
info@discoverypublishinggroup.com
parul.wasan@gmail.com
web: www.discoverypublishinggroup.com