Earthing strip size for
transformer. 
Cross Section Area of Earthing Conductor As per IS
3043 
A = (If x√t) / K  
Where:
t
= Fault current Time (Second)., 1 sec or 3 sec
K
= Material Constant, Material Constant, For GI=80, copper K=206, Aluminium
K=126).
Part-A:
Typical Protective conductor size required for Transformer Ratings
(100-500KVA)
| 
   | 
  
   | 
  
   | 
  
   | 
  
   | 
 ||
| 
   
Sr.  
 | 
  
   
A 
 | 
  
   
B 
 | 
  
   
C 
 | 
  
   
D 
 | 
  
   
E 
 | 
  
   
F 
 | 
 
| 
   
1 
 | 
  
   
Transformer Rating ( KVA) 
 | 
  
   
100 
 | 
  
   
160 
 | 
  
   
250 
 | 
  
   
315 
 | 
  
   
500 
 | 
 
| 
   
2 
 | 
  
   
Secondary Voltage (V) 
 | 
  
   
433 
 | 
  
   
433 
 | 
  
   
433 
 | 
  
   
433 
 | 
  
   
433 
 | 
 
| 
   
3 
 | 
  
   
Full Load current 
 | 
  
   
133 
 | 
  
   
213 
 | 
  
   
333 
 | 
  
   
420 
 | 
  
   
667 
 | 
 
| 
   
4 
 | 
  
   
Percentage Impedance Z% 
 | 
  
   
5 
 | 
  
   
5 
 | 
  
   
5 
 | 
  
   
5 
 | 
  
   
5 
 | 
 
| 
   
5 
 | 
  
   
Short Circuit Current (SC) in A =FLC*(100/Impedance) 
 | 
  
   
2660 
 | 
  
   
4260 
 | 
  
   
6600 
 | 
  
   
8400 
 | 
  
   
13340 
 | 
 
| 
   
6 
 | 
  
   
Area of Protective conductor Reqd in sq.mm = SC *√t/k 
 | 
  
   | 
  
   | 
  
   | 
  
   | 
  
   | 
 
| 
   
7 
 | 
  
   
t = 1 Sec 
 | 
  
   | 
  
   | 
  
   | 
  
   | 
  
   | 
 
| 
   
8 
 | 
  
   
Copper k = 206 
 | 
  
   
12.9 
 | 
  
   
20.7 
 | 
  
   
32.0 
 | 
  
   
40.8 
 | 
  
   
64.8 
 | 
 
| 
   
9 
 | 
  
   
Recommended strip size 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 3 mm 
 | 
 
| 
   
10 
 | 
  
   
Alluminium k = 126 
 | 
  
   
21.1 
 | 
  
   
33.8 
 | 
  
   
52.4 
 | 
  
   
66.67 
 | 
  
   
105.9 
 | 
 
| 
   
11 
 | 
  
   
Recommended strip size 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 6 mm 
 | 
 
| 
   
12 
 | 
  
   
Steel, k= 80 
 | 
  
   
33.3 
 | 
  
   
53.3 
 | 
  
   
82.5 
 | 
  
   
105 
 | 
  
   
166.8 
 | 
 
| 
   
13 
 | 
  
   
Recommended strip size 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 6 mm 
 | 
  
   
25 x 6 mm 
 | 
  
   
40 x 6 mm 
 | 
 
| 
   
14 
 | 
  
   
t =3 Sec 
 | 
  
   | 
  
   | 
  
   | 
  
   | 
  
   | 
 
| 
   
15 
 | 
  
   
Copper k = 206 
 | 
  
   
22.34 
 | 
  
   
35.85 
 | 
  
   
56.42 
 | 
  
   
70.67 
 | 
  
   
112.23 
 | 
 
| 
   
16 
 | 
  
   
Recommended strip size 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 6 mm 
 | 
 
| 
   
17 
 | 
  
   
Alluminium k = 126 
 | 
  
   
36.55 
 | 
  
   
58.54 
 | 
  
   
90.76 
 | 
  
   
115.47 
 | 
  
   
183.42 
 | 
 
| 
   
18 
 | 
  
   
Recommended strip size 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 6 mm 
 | 
  
   
25 x 6 mm 
 | 
  
   
40 x 6 mm 
 | 
 
| 
   
19 
 | 
  
   
Steel , k= 80 
 | 
  
   
57.68 
 | 
  
   
92.32 
 | 
  
   
142.89 
 | 
  
   
181.86 
 | 
  
   
288.9 
 | 
 
| 
   
20 
 | 
  
   
Recommended strip size 
 | 
  
   
25 x 3 mm 
 | 
  
   
25 x 6 mm 
 | 
  
   
25 x 6 mm 
 | 
  
   
40 x 6 mm 
 | 
  
   
50 x 6 mm 
 | 
 
PART-B:
Typical Protective conductor size required for Transformer Ratings
(630-2000KVA)
| 
   
Sr.  
 | 
  
   
A 
 | 
  
   
G 
 | 
  
   
H 
 | 
  
   
I 
 | 
  
   
J 
 | 
  
   
K 
 | 
  
   
L 
 | 
 
| 
   
1 
 | 
  
   
Transformer Rating ( KVA) 
 | 
  
   
630 
 | 
  
   
750 
 | 
  
   
1000 
 | 
  
   
1250 
 | 
  
   
1600 
 | 
  
   
2000 
 | 
 
| 
   
2 
 | 
  
   
Secondary Voltage (V) 
 | 
  
   
433 
 | 
  
   
433 
 | 
  
   
433 
 | 
  
   
433 
 | 
  
   
433 
 | 
  
   
433 
 | 
 
| 
   
3 
 | 
  
   
Full Load current 
 | 
  
   
840 
 | 
  
   
1000 
 | 
  
   
1333 
 | 
  
   
1667 
 | 
  
   
2133 
 | 
  
   
2667 
 | 
 
| 
   
4 
 | 
  
   
Percentage Impedance Z% 
 | 
  
   
5 
 | 
  
   
5 
 | 
  
   
5 
 | 
  
   
6 
 | 
  
   
6 
 | 
  
   
6 
 | 
 
| 
   
5 
 | 
  
   
Short Circuit Current (SC) in A 
 | 
  
   
16801 
 | 
  
   
20001 
 | 
  
   
26668 
 | 
  
   
27779 
 | 
  
   
35558 
 | 
  
   
44447 
 | 
 
| 
   
6 
 | 
  
   
Area of Protective conductor Reqd in sq.mm = SC *√t/k 
 | 
  
   | 
  
   | 
  
   | 
  
   | 
  
   | 
  
   | 
 
| 
   
7 
 | 
  
   
t = 1Sec 
 | 
  
   | 
  
   | 
  
   | 
  
   | 
  
   | 
  
   | 
 
| 
   
8 
 | 
  
   
Copper k = 206 
 | 
  
   
81.96 
 | 
  
   
97.57 
 | 
  
   
130.09 
 | 
  
   
135.51 
 | 
  
   
173.45 
 | 
  
   
216.81 
 | 
 
| 
   
9 
 | 
  
   
Recommended strip size 
 | 
  
   
25 x 6 mm 
 | 
  
   
25 x 6 mm 
 | 
  
   
25 x 6 mm 
 | 
  
   
25 x 6 mm 
 | 
  
   
40 x 6 mm 
 | 
  
   
40 x 6 mm 
 | 
 
| 
   
10 
 | 
  
   
Alluminium k = 126 
 | 
  
   
133.34 
 | 
  
   
158.74 
 | 
  
   
211.65 
 | 
  
   
220.47 
 | 
  
   
282.2 
 | 
  
   
352.75 
 | 
 
| 
   
11 
 | 
  
   
Recommended strip size 
 | 
  
   
25 x 6 mm 
 | 
  
   
40 x 6 mm 
 | 
  
   
40 x 6 mm 
 | 
  
   
40 x 6 mm 
 | 
  
   
50 x 6 mm 
 | 
  
   
75 x 6 mm 
 | 
 
| 
   
12 
 | 
  
   
Steel, k= 80 
 | 
  
   
210.01 
 | 
  
   
250.01 
 | 
  
   
333.35 
 | 
  
   
347.24 
 | 
  
   
444.47 
 | 
  
   
555.59 
 | 
 
| 
   
13 
 | 
  
   
Recommended strip size 
 | 
  
   
40 x 6 mm 
 | 
  
   
50 x 6 mm 
 | 
  
   
75 x 6 mm 
 | 
  
   
75 x 6 mm 
 | 
  
   
75 x 6 mm 
 | 
  
   
75 x10 mm 
 | 
 
| 
   
14 
 | 
  
   
t =3 Sec 
 | 
  
   | 
  
   | 
  
   | 
  
   | 
  
   | 
  
   | 
 
| 
   
15 
 | 
  
   
Copper k = 206 
 | 
  
   
141.26 
 | 
  
   
168.17 
 | 
  
   
224.22 
 | 
  
   
233.56 
 | 
  
   
298.96 
 | 
  
   
373.7 
 | 
 
| 
   
16 
 | 
  
   
Recommended strip size 
 | 
  
   
25 x 6 mm 
 | 
  
   
40 x 6 mm 
 | 
  
   
40 x 6 mm 
 | 
  
   
40 x 6 mm 
 | 
  
   
50 x 6 mm 
 | 
  
   
75 x 6 mm 
 | 
 
| 
   
17 
 | 
  
   
Alluminium k = 126 
 | 
  
   
230.95 
 | 
  
   
274.94 
 | 
  
   
366.58 
 | 
  
   
381.86 
 | 
  
   
488.78 
 | 
  
   
610.97 
 | 
 
| 
   
18 
 | 
  
   
Recommended strip size 
 | 
  
   
40 x 6 mm 
 | 
  
   
50 x 6 mm 
 | 
  
   
75 x 6 mm 
 | 
  
   
75 x 6 mm 
 | 
  
   
75 x 10 mm 
 | 
  
   
75 x 10 mm 
 | 
 
| 
   
19 
 | 
  
   
Steel , k= 80 
 | 
  
   
363.74 
 | 
  
   
433.03 
 | 
  
   
577.37 
 | 
  
   
601.42 
 | 
  
   
769.82 
 | 
  
   
962.28 
 | 
 
| 
   
20 
 | 
  
   
Recommended strip size 
 | 
  
   
75 x 6 mm 
 | 
  
   
75 x 6 mm 
 | 
  
   
75 x10 mm 
 | 
  
   
75 x10 mm 
 | 
  
   
100 x 10 mm 
 | 
  
   
100 x 10 mm 
 | 
 
Reader
can choose safely factor as 1.5. 
Suppose
calculated strip size is 40x6 sqmm = 240sqmm
Considering
safety factor , strip size = 240x1.5 = 360 sqmm.
Electrode
always should be installed in 2 and opposte side of equipment. The distance
between electrode is not less than height of one electrode.