Bonding
of lightning down conductor and earth electrode
Ref: NEC 250.106 and NFPA 780 section 4.14.
·
The electrical system and
communications grounding electrodes, along with all incoming or exiting
metallic piping in the earth must be bonded to the lightning-protection
grounding electrode system.
·
Connections between the down
conductors of lightning arrester and grounding electrodes may be made by
bolting, brazing, and welding or high compression connector.
earthing at telecom, data center, computer network |
·
Clamps suitable may also be
used.
·
Where more than one utility exists
at a building or structure, they shall be effectively bonded together to form a
common grounding electrode system and the MGB (main grounding bus bar). For example: a metallic underground water
pipe, the metal frame of the building or structure, concrete-encased electrode,
a ground ring conductor encircling the building or structure, rod or pipe
electrodes and lightning electrodes etc. (Ref: NFPA 70-2005).
Resistance value:
equal or less than 5 ohm
ReplyDeleteReally very interesting and informative Post. Keep sharing blogs with us.
coimbatore electricity bill payment
torrent power bill payment
punjab electricity bill payment
north bihar electricity bill payment
secure online bill payment
Thanks for sharing this informative post ! Ensure seamless operation of telecommunication systems with Axis Electricals' dependable earth bus bars. Visit us to learn about our products!
ReplyDeleteWow, I came to learn about machines, and your information is absolutely amazing! For more insights and if your are looking for the Grounding Electrode
ReplyDelete! We specialize in reliable solutions to meet all your Grounding Electrode needs. Keep up the great work!