Sunday 12 July 2020

Earthing at telecom exchange, data centre, IT console, network control room


Bonding of lightning down conductor and earth electrode
Ref:  NEC 250.106 and NFPA 780 section 4.14.
·         The electrical system and communications grounding electrodes, along with all incoming or exiting metallic piping in the earth must be bonded to the lightning-protection grounding electrode system.
·         Connections between the down conductors of lightning arrester and grounding electrodes may be made by bolting, brazing, and welding or high compression connector.
earthing at telecom, data center, computer network
·         Clamps suitable may also be used.
·         Where more than one utility exists at a building or structure, they shall be effectively bonded together to form a common grounding electrode system and the MGB (main grounding bus bar).  For example: a metallic underground water pipe, the metal frame of the building or structure, concrete-encased electrode, a ground ring conductor encircling the building or structure, rod or pipe electrodes and lightning electrodes etc. (Ref: NFPA 70-2005).
Resistance value: equal or less than 5 ohm

2 comments:

  1. Thanks for sharing this informative post ! Ensure seamless operation of telecommunication systems with Axis Electricals' dependable earth bus bars. Visit us to learn about our products!

    ReplyDelete

SOP, Standard Operating Procedures

  1.1 .    Definition SOP is termed commonly as Standard Operating Procedures- SOP  Characteristics of SOP- 1)     Carry out the operati...