SUBSTATION HEALTHINESS CHECK
substation healthiness |
a) Substation overall
1
|
Are all doors and windows locked?
|
2
|
Are all doors/shutters opening and closing smoothly?
|
3
|
Are all windows opening and closing smoothly?
|
4
|
L-drops/Tower bolts available on each door, both from inside as well as outside
|
5
|
Are window panes of all windows are in order?
|
6
|
Are there any gaps beneath the fully closed door/shutter?
|
7
|
Is DC Emergency Lights working?
|
8
|
Is Pressurization system working & what is the date of last filter cleaning?
|
9
|
Check the pressure differential and see if it is within normal limits. Record it.
|
10
|
Is Do's and Don'ts board available?
|
11
|
Is Updated SLD board available?
|
12
|
Is List of authorised persons/entrants available?
|
13
|
Is Shock treatment chart available?
|
14
|
Are Cable trench openings fully covered?
|
15
|
Are Filled sand buckets/tested fire extinguishers in appropriate numbers available?
|
16
|
Is the cable cellar free from garbage and unwanted materials?
|
17
|
Is the cable cellar well lit and free from obstructions?
|
18
|
While examining from the cellar are all the ingoing cables entries/ holes well sealed?
|
19
|
Is the substation being regularly dusted/ mopped?
|
20
|
Are the Insulating mats provided in front of all the switchgear panels?
|
21
|
Check whether thermometer and Humidity measuring device is in order. Record the
readings. |
b) Transformer yard
1
|
Is it Easily Accessible?
|
2
|
Is there any growth of Wild grass/vegetation?
|
3
|
How is the Cleanliness (inside/outside)?
|
4
|
Is the yard properly fenced and danger board provided at a visible place?
|
5
|
Are Gates kept locked?
|
6
|
Are the terminal boxes completely sealed?
|
7
|
Is there any Gap/hole in cable entry bottom plate?
|
8
|
Is the physical appearance of Silica gel OK?
|
9
|
Is Transformer oil level ok?
|
10
|
Is there any oil leakage on the transformer tank surface?
|
11
|
Are filled sand buckets/ tested fire extinguishers available in the yard?
|
12
|
Are the neutral grounding electrode pits in good condition?
|
13
|
Are there any traces of oil leakage into the electrode pits?
|
14
|
Is the transformer surface paint in good condition?
|
15
|
Check for any abnormal humming noise emanating from the transformer.
|
c) Battery room
1
|
Check if Light fittings & exhaust fan are flameproof construction and in working condition.
|
2
|
Check for any abnormal temperature of cells.
|
3
|
Check for electrolyte leakage from cells, if any.
|
4
|
Check for availability of tools and tackles like hand gloves, apron, electrolyte drums, funnel etc. in Battery room.
|
5
|
Check for continuous availability of water in the Battery room.
|
6
|
Is Shock treatment chart available?
|
d) Sealing of hole in HT/ LT Switchgear /DCDB/ Chargers/ VFD panels etc.
1
|
Are Holes/cut-outs in front/back side of the panel properly covered/closed?
|
2
|
Are Front/back covers of all the feeders/breakers closed properly?
|
3
|
Are Relay modules/control cabinets of all the feeders/breakers closed properly?
|
4
|
Are any gaps through front/back covers/relay modules/control cabinets of all the feeders/breakers sealed properly?
|
5
|
Are all panel screws found in place and tightened properly?
|
6
|
Are all extra holes/cut-outs or part of these holes/cut-outs on panel completely sealed?
|
7
|
Are any gaps at the panel door hinges/side covers/ top covers properly sealed?
|
8
|
Are panel door gaskets in good condition?
|
8
|
Is there any dust/spider web on any part of the panel?
|
9
|
Are all the extra holes in the bottom cable entry plate and gaps through existing cables completely sealed (Applicable for panels under shutdown)?
|
10
|
Check whether Indication lamps are in working condition.
|
11
|
Check if any relay abnormal operation has occurred. Investigate and then reset.
|
e) FLP Equipments
1
|
Check flame proofness of FLP equipments e.g., Lighting Luminaries, JBs, DBs, PBSs etc.
|
2
|
Check that the glanding is proper and with FLP Double Compression cable gland.
|
3
|
Check the Terminal Blocks of FLP equipments for tightness & cleanliness.
|
4
|
Check availability of all the Allen Bolts on FLP fittings/JBs/ DBs etc. Provide, if not