Fuse (Amp) Selection
for Protection of Transformer
transformer size in KVA
|
6.6KV
|
11KV
|
22KV
|
25
|
10
|
6
|
|
50
|
20
|
10
|
6
|
75
|
25
|
16
|
6
|
100
|
32
|
20
|
10
|
150
|
40
|
32
|
16
|
200
|
50
|
32
|
20
|
250
|
63
|
40
|
25
|
315
|
63
|
50
|
32
|
400
|
80
|
63
|
32
|
500
|
100
|
63
|
40
|