Electrical Safety and OISD -234
Safety in Electrical
System deserves maximum attention especially in the hydrocarbon industry, where
electricity constitutes one of the major sources of ignition that could cause a
fire or an explosion.
Hazardous Area
classification shall be followed and should be carried out in line with
OISD-STD-113 and IS: 5572. Accordingly,
the electrical equipment / fittings should be selected in line with IS: 5571.
Area classification:
ZONE - 0: An area in
which a flammable atmosphere is continuously present.
ZONE-1: An area in
which a hazardous atmosphere is likely to occur under normal operating
condition.
ZONE-2: An area in
which a hazardous atmosphere is likely to occur only under abnormal operating
conditions likely to occur under normal operating condition.
Note: Approval from
DGMS(Directorate General of Mines Safety ) shall be available for
equipment used in hazardous area
EARTHING
SYSTEM
Earthing
system design shall be carried out in accordance with the requirements of CEA
regulations 2010 and IS:3043.
PLANT EARTHING
i) Earthing system in
general, shall cover the following:
- Equipment earthing
for personnel safety,
- System neutral
earthing, and
- Static and lightning
protection.
ii) The earthing
system envisages an earthing network with designed number of earth electrodes
attached to it. The following shall be earthed:
Earthing coverage
a) Metallic non-current carrying
parts of all electrical apparatus such as
transformers, switchgears, motors, lighting/power panels, terminal
boxes, control stations, lighting fixtures, receptacles etc.
b) Current and potential transformer
secondary neutral System Neutral
c) Steel structures, Loading
platform etc.
d) Metallic Cable trays and racks,
lighting mast and poles.
e) Storage tanks, spheres, vessels,
columns and all other process equipment.
f) Electrical equipment fencing
(e.g. transformer, yard etc.)
g) Cable shields and armour
h) Flexible earth provision for Tank
Wagon, Tank Truck
Earth resistance value
The maximum resistance
value of an earthing system to the general mass of earth should not exceed:
a)
4 ohms for electrical systems and
metallic structures.
b)
7 ohms for storage tanks.
c)
1 Ohm for main earth grid
Minimum Size of
earthing conductors for electrical equipment
Sr. No.
|
Type of equipment
|
Earth Conductor Size
|
1
|
Building Columns
|
40mmx5mm GI strip
|
2
|
Storage tanks (vertical
&horizontal)
|
40mmx5mm GI strip
|
3
|
Loading racks
|
40mmx5mm GI strip
|
4
|
Pipe racks , vessels,
& heat exchanger
|
40mmx5mm GI strip
|
5
|
Motor upto 3.7KW
|
8 SWG solid GI wire
|
6
|
Motor upto
5.5KW30KW&welding receptacle
|
10 mm dia GI wire rope
|
7
|
Motor upto 37KW and above
including HV motors
|
10 mm dia GI wire rope or
40mmx5mm GI strip
|
8
|
Small equipment of
instrument
|
8 SWG solid GI wire /rope
|
9
|
Push button station
|
8 SWG solid GI wire
|
10
|
Lighting, power
instruments, panels
|
10 mm dia GI wire rope
|
11
|
Street light poles
|
10 mm dia GI wire rope
|
12
|
Lighting transformer
|
16 mm dia GI wire rope
|
13
|
Bonding of pipe
|
25 sqmm insulated flexible
copper cable
|
14
|
MV/HV bus duct, power
transformer
|
As per calculation
|
15
|
HV&EHV substation
|
As per calculation
|
16
|
LA (5KA,9KA)
|
25×3 mm Cu Strip
|
17
|
HT Switchgear
|
50×6 mm GI Strip
|
18
|
Structure
|
50×6 mm GI Strip
|
19
|
Fence / Rail Gate
|
50×6 mm GI Strip
|
20
|
Cable tray
|
50×6 mm GI Strip
|
PROTECTION AND
METERING
The protective system
shall be selected and coordinated to ensure the following:
a. Protection of
equipment against damage which can occur due to internal or external short
circuits, overloading, abnormal operating conditions, switching, lightning
surges, etc.
b. The continuity of
operation is maintained to those parts of the system not affected by the fault.
c. Personnel and plant
safety-
Relays and protective devices shall be suitably
selected and coordinated.
ii) Recommended relay
protections for Transformers, motors and feeders which are generally
encountered in distributing network.
EMERGENCY POWER SUPPLY
-Electrical
loads essential for the safe shutdown of the plant.
-
Emergency lighting, security lighting, obstruction lights.
-
Process plant instruments as required.
-
Communication equipment, Fire Alarm control panels.
-
Firefighting equipment excluding main fire water pumps.
-
Loads critical for process, plant and personnel safety.
Note: within a period
not exceeding 30 seconds from the instant of failure of normal supply
Critical Power Supply
Systems- UPS or DC Power Supply
in the event of
Normal/ Emergency supply failure –
-
Critical Lighting system
-
Critical instrumentation and process control,
-
Critical communication like telephone,
walky-talky (VHF) equipment,
-
Fire and Gas detection system
SUBSTATION LOCATION /
LAYOUT
·
Sufficient space in front
and back to allow access for cable terminations , maintenance and
inspection of equipment.
·
Cable trenches, wherever provided,
inside sub-stations shall be filled with sand and to be shield.
·
Fire extinguishers, suitable for
electrical fires (CO2 type) and round bottom fire buckets with clean dry sand.
·
Each substation building shall have at
least two doors.
·
to locate DG sets in a separate
house/shed away from Substation in a safe area.
·
adequate clearances between equipment,
and equipment.
·
The battery room shall be a separate
and freely ventilated room.
Note: the battery room
and walls up to height of one meter shall have acid resisting material/coating.
ELECTRICAL
EQUIPMENT
¨ should
preferably have winding temperature indicators with alarm / trip provisions.
¨ B.
HIGH VOLTAGE (H.V) /MEDIUM VOLTAGE (M.V) SWITCHBOARDS
-To
ensure maximum safety during operation, inspection.
-Switchboard
shall be totally enclosed, dust and vermin proof.
-Barriers
shall be provided to permit personnel to work safely.
-Suitable
interlocks .
-Insulating
mats of appropriate voltage level (conforming to IS-15652.
-Panels
shall be painted with the description of its identification at front and at the
rear.
-Starting
of motors from substation shall not be allowed.
-All
H.V. switchgears should have provision of view glasses/ IR windows.
MOTORS HIGH VOLTAGE
(H.V.) & MEDIUM VOLTAGE (M.V)
i) Ingress protection
for motor should preferably be IP 44 for indoor use and IP 55 for outdoor duty motors.
ii) The permissible
noise as per Pollution Control Board (CPCB) guidelines.
iii) winding
insulation shall be class F and temperature rise limited to that specified in
the applicable IS for class B insulation .
EMERGENCY GENERATOR
i) shall be designed to start automatically on power failure and feed the
selected loads.
ii) Diesel Engine installation, do not call for Area Classification,
provided the D.G. room is properly ventilated.
ii) DG sets shall comply with the latest guidelines of environment
ministry with regard to noise levels.
iii) OISD STD 127 to be referred for details on operation, inspection
& maintenance of Diesel Engines.
CONTROL STATION
i) Each Motor shall be provided with a control station in the field, a
STOP push button as a minimum.
ii) Enclosure shall have suitable protection as per hazardous area
classification.
iii) It includes individual process requirements: - Start/stop push button, close/ neutral/,
Trip Switch, Ammeter.
Iv) Local/Remote Selector Switch.
V) Auto/Manual selector switch and cable glands.
Plant lighting
i) In addition to the normal lighting, each installation shall be
equipped with emergency and critical lighting.
ii) Critical lighting shall enable safe evacuation of operating personnel
and shall be employed along escape route, assembly point and critical
installations such as first aid centre, control rooms, manned sub-stations,
fire water pump house etc.
iv) For hazardous areas, emergency lighting fixtures shall be explosion
proof Ex(d) type, irrespective of the area being classified as zone-1 or
zone-2.
v) Voltage 250V, if the neutral or the midpoint of the system is
connected with earth.
PRE-COMMISSIONING CHECKS
i) The statutory clearances from the State Electrical
Inspectorate/Director General, Mines Safety.
ii) Manufacturer’s test certificates shall be obtained (for the
successful passing of shop tests.
iii) Installations conform to acceptable engineering standards and are
appropriate to the respective hazardous area classifications.
Generator
- Electrical checks/ testing as recommended by OEM
- Condition of terminal box: tightness of nuts & bolts, missing
bolts, condition of bushings.
- Foundation bolts –Tightness
- Check terminal bushings for any damage or looseness
- Checking of exciter/field/stator coils, AVR, Rectifier Bridge, brushes,
surge suppressor or variable resistor (varistor) etc.
- Healthiness of protection circuits.
- Proper functioning of Space Heaters.
- Protection circuits (testing and simulation tests)
- Auto/manual starting and changeover system
- Earthing connection and record Insulation Resistance
- Measure & record PI (polarization Index) value, greater than 2.
- Earth resistance value & test date on the earth pit cover.
Electric Motor
-Electrical checks/ testing as recommended by OEM.
- Condition of terminal box: nuts & bolts tightened, missing bolts.
- Cable termination (size and type of cable).
- Driving end condition:
- Non driving end condition:
- Foundation bolts -Tightness
- Insulation Resistance value
- Space heater where provided.
- Motor on no-load test
ELECTRICAL PANELS
-Electrical checks/
testing as recommended by OEM
- All incomer and
outgoing, bus bar, support insulators, phase barriers
- Functionality check/
testing of CBs, MCCBs, CT, PT, Bus Bar, protection relays, Energy meters, Power
Packs etc.
- Operation of
interlocks and safety devices.
- Insulation resistance
measurement for Bus Bar, power cables, Breakers.
- Switchgear panel
earthing by two separate and distinct connections to earth.
- Primary injection
testing of switchgear Incomer and Outgoing panels.
- Secondary injection
testing of protection relays
- Electrical &
manual closing and tripping of all circuit breakers (remote and local)
- Check Circuit
Breakers for proper racking-in and rack-out operation.
TRANSFORMER AND
BUS-DUCT
-Electrical checks/
testing as recommended by OEM.
- Body and neutral
earthing/ earth resistance
- Check insulation
resistance and PI of HV and LV windings.
- Dielectric strength
of Transformer oil (as per IS : 335)
- Oil level in the
conservator, bushings and thermometer pockets
- Operation of the tap
changer circuits on all the tap positions (simulation)
- Functioning of
Buchholz relay
-Checking/ testing of
marshalling panel
-Oil/ winding alarm/
trip ckt. simulation.
-Protection system
checking.
- Cooling system
(automatic starting and stopping of fans)
- Sealing of bus duct
entries through walls (for vapour, dust, water tightness)
PRECAUTIONS DURING
LOADING AND UNLOADING OF PETROLEUM TANKERS
1. In the loading and
unloading area all pipe-lines, fittings and delivery hoses or metal pipes,
metallic loading arms, swivel joints, tanks, chassis of tankers shall be
electrically continuous and be efficiently earthed.
2. No mechanically
propelled tankers shall be loaded or unloaded until its engine has been stopped
and battery isolated from electrical circuit.
3. The engine shall
not be restarted and the battery shall not be connected to the electrical
circuit until all tanks, and valves have been securely closed:
4. Adequate
Fire-Fighting equipment shall be kept readily available during loading of
tankers for immediate use
DISPLAY OF CAUTION
BOARDS
i. Electrical Caution
Board on electrical equipment when under maintenance or repair
“DO NOT OPERATE, MEN
at WORK”
ii. Notice for
restricted entry in Electrical control room / Substation
“ENTRY OF UNAUTHORISED
PERSONS PROHIBITED
PERSONAL PROTECTIVE
EQUIPMENT (PPEs)
-Insulating
mats conforming to IS:15652
-
Safety Shoes
-
Fuse handling equipment
-
Goggle/ Face Shield
-
Electrical discharging/ Earthing Rod
-
Gas masks (for generating station with capacity 5MW or above)
-
Safety helmet
-
Safety Belt
-
Safety Torch
DISPLAY
AT SUBSTATION/ CONTROL ROOM
i.
Single line diagram
ii.
Hazardous area classification of the location
iii.
Electrical Shock Treatment Chart
iv.
Important / emergency telephone numbers
v.
Isolation / lock –out tags
vi.
Escape route
RECORD
KEEPING (AS APPLICABLE):
i.
Attendance Register
ii.
Shift Roster
iii.
List of trained First Aid & Firefighting personnel
iv.
List of persons with Electrical License (wiremen & supervisory)
v.
Accident Records
vi.
Log Book & equipment maintenance record
vii.
Daily check list of electrical equipment
viii.
Earth Resistance & Insulation Resistance Record
ix.
Work Permits
x.
Lay out Drawings
xi.
Equipment/Earthing/Cable
Standard
BIS (Bureau of Indian
Standards) Publications
* IS 5571 Guide for
selection of electrical equipment for hazardous areas.
* IS 5572
Classification of Hazardous area having flammable gases and vapour for
electrical installation.
* IS 7820 Electrical
Apparatus for Explosive Gas Atmospheres - Method of Test for Ignition
Temperature
* IS 3043 Code of
Practice for Earthing.
* IS 2309 Code of
practice for the protection of buildings and allied structures against lightning
* IS 15652 Insulating
mats for electrical purposes
* DGMS letter No. 1
(6) 2001- Genl / 3604 -3753
*CA regulation 2010
WORK PERMIT SYSTEM:
Work Permit System shall be followed as per OISD STD 105 .
Loto
OISD 234 |
MINIMISING EQUIPMENT FAILURE
1. Proper functioning of
electrical equipment can only be ensured by means of periodic preventive and
predictive maintenance of the equipment. This enhances equipment life and also
ensures safety of the equipment, installation and operating personnel.
2. Maintenance may be daily,
weekly, quarterly or annual depending upon the type of equipment. Adequate logs
shall be maintained to ensure that maintenance is carried out as per approved
checklists. Preventive maintenance should be carried out as per schedules laid
down in OISD STD- 137.
3. Live parts of switch gear
shall be made inaccessible from any inadvertent physical contact, lizard entry
etc. These shall be suitably covered by barriers and shrouds.
4. It shall be ensured that the
electrical installation shall be rust / corrosion protected. This should be
achieved by painting all equipment at regular intervals by use of zinc
passivated, nickel plated hardware, stainless steel hardware, through provision
of canopies for outdoor equipment and covering of terminal boxes to prevent
ingress of water etc. Battery rooms
shall be kept
dry and well ventilated and all terminals shall be kept covered with petroleum
jelly to avoid corrosion.
5. During
maintenance if any equipment is removed from panel doors, etc. which leaves an
open cutout on the equipment, the same shall be promptly sealed using blanking
plates or
other means, to
ensure that there is no loss of the degree of ingress protection and also that
this does not provide a means of access for entry of dust / vermin etc. It
shall be ensured that all unused cable entries are blanked off.
6. All battery
banks shall be routinely checked for healthy cell voltage, specific gravity of
cells, electrolyte level etc.
7. Insulation
resistance of all electrical equipment, such as, all switchboards, motors,
transformers, cables etc. shall be routinely measured and logged to ensure
healthiness of equipment.
8. Dielectric
strength of transformer insulating oil, Oil Circuit Breakers etc. shall be
measured at regular intervals and recorded and oil filtration shall be carried
out wherever necessary. Dissolved Gas analysis for transformers rated 5MVA and
above may be carried out as a predictive method to assess health of transformer.
9. All cable
terminations, bus-bar joints, etc. shall be tightened, more so for equipment
subjected to vibrations, to ensure that there are no hot spots which could lead
to fire / equipment failure.
10. Settings of
protective relays shall be checked to ensure that they are set as per the
recommended settings. Protective Relays shall be tested / calibrated once a
year to ensure proper operation as per manufacturer’s recommendations.
11. Unused cable
entries in any switchboard / Electrical installation shall not be kept open.
12. Conduits
used for cable entry shall be sealed and earthed.
13. All wall
openings of an electrical substation including cable entries shall be properly
sealed
to arrest water
entry inside substation.
14. Transformer
and switchyards shall be maintained free of vegetation / dry grass.
15. Earth grid
resistance shall be measured and recorded regularly to ensure operation of
related protective devices in case of fault.
16. All electric
apparatus and wiring in a hazardous area shall at all times be so maintained as
to retain the characteristic on which their approval has been granted
17. Equipment enclosures and
fittings shall be examined to see that all stopping plugs and bolts are in
position and properly tightened. Locking and sealing devices shall be checked
to ensure that they are secured in prescribed manner.
18. Replacement
fasteners, nuts, studs and bolts shall be of the type specified by the
manufacturer for the particular apparatus. No attempt shall be made to replace
or repair a glass in a flameproof enclosure e.g. in a luminaire or other
enclosures, except by replacement with the complete assembly or part obtainable
from the manufacturer, complying with the approval certificate.
19. If at any
time, there is a change in the area classification or in the characteristics of
the flammable material handled in the area or if the equipment is relocated in
the area, the area classification drawing should be correspondingly revised and
a check shall be made to ensure that the equipment selection corresponds to the
revised area classification.
20. A system
shall be established to record the results of all inspections and the action
taken to correct defects.
You wrote a great blog on Electrical Safety. We Elegrow Technology established in 2003 offering effective Design, Service and Up-gradation Solution for industrial, Commercial, Agricultural and Corporate sectors. The company is consisting of highly-qualified and experienced engineers.
ReplyDeleteThanking a lot to you for sharing the useful information....
ReplyDeleteLED Explosion Proof Lights
Data Centre Lighting
Thanks for sharing this information. your blog is good and I got so much knowledge...
ReplyDeleteIndustrial PPE supplier
Tungsram Lamps
Thank you for sharing the valuable content.
ReplyDeleteBattery testing equipment determine the condition of lead-acid and nickel-cadmium cells ,String, Battery capacity, Electrical power. Robust,repeatable instruments, Measures float and ripple currents.
I am thankful for this blog to gave me much knowledge regarding my area of work. I also want to make some addition on this platform which must be in knowledge of people who really in need. Thanks. Emergency & Safety Lighting
ReplyDeletePoor electric installation can have serious consequences, including frequent power outages, tripping breakers, and increased energy bills. It's important to address any signs of faulty installation, such as loose connections or exposed wiring, to prevent further damage and ensure the longevity of your electrical system. Don't let poor installation undermine your electrical infrastructure!
ReplyDeleteNice articles and your information valuable and good articles thank for the sharing information MV Switchgear
ReplyDelete