The following earthing systems and design fault
currents (3-phase symmetrical) are in use throughout the distribution network.
Voltage
|
Type
of earthing
|
Fault
current
|
Fault
level
|
132KV
|
Slid
earthing
|
21.9
KA
|
5000
MVA
|
33
KV
|
Impedance
earthed
|
17.5
KA
|
1000
MVA
|
11
KV
|
Impedance
earthed
|
13.1
KA
|
250
MVA
|
6.6
KV
|
Impedance
earthed
|
21.9
KA
|
19.4
MVA
|
<
650V
|
Slid
earthing
|
27
KA
|
|
Where the network is impedance earthed the typical
neutral earth resistor will limit the earth fault current to 1000A per
transformer, i.e. giving a maximum earth fault level of up to 3kA.
Design earth fault
clearance times are:
VOLTAGE CLEARANCE
TIME
132 KV 200ms
( mili second)
33 KV 500ms
6.6/11 KV 1s
Short
circuit current, Isc (kA) at the LV terminals of a 3-phase HV/LV transformer.
Transformer
rated power (kVA)
|
100
|
315
|
500
|
800
|
1000
|
1250
|
1600
|
2000
|
2500
|
Transformer
rated (LV) current (A)
|
137
|
433
|
687
|
1100
|
1375
|
1718
|
2199
|
2749
|
3437
|
Psc =
250MVA
|
33.1
|
8.38
|
13.2
|
17.4
|
20.4
|
21.5
|
26.4
|
40.4
|
49.1
|
|
|
|
|
|
|
|
|
|
|