Relay no | Description |
2 | Time delay starting or closing |
3 | Checking/interlocking |
4 | Master contactor |
21 | Distance relay |
25 | Synchronizing relay |
27 | Under voltage relay |
30 | Enunciators relay |
32 | Directional power |
37 | Under current/ under power |
40 | Field failure |
46 | Phase balance current |
49 | Machine/transformer thermal |
50 | Instantaneous over current or rate of rise |
51 | AC time over current |
52 | AC circuit breaker |
52a | Circuit breaker auxiliary contact NO |
52b | Circuit breaker auxiliary contact NC |
55 | Power factor relay |
56 | Field application relay |
59 | Over voltage |
60 | Voltage or current balance |
64 | Earth fault |
67 | AC directional over current |
68 | Blocking relay |
74 | Alarm |
76 | DC over current |
78 | Phase angle measuring or out of step |
79 | AC re-closing |
81 | Frequency relay |
83 | Automatic selective control |
85 | Carrier or pilot wire receiver |
86 | Locking out or master trip |
87 | Differential protection |
94 | Anti pumping |
95 | Supervision |
96 | Bus differential |
63 | Buchholz relay |
49 | Transformer winding /oil temperature |
SHORT TAXT | |
CAG14 | High impedance differential relay with variable current setting |
CDAG | Over current relay with time delayed phase fault elements having any of the standard inverse characteristic plus an instantaneous earth fault element |
CDG11 | Inverse time over current relay with basic inverse time characteristic and a single contact on the disc |
CDV22 | Voltage controlled inverse time overcurrentrelay |
CTN | Negative phase sequence with inverse time characteristics for generator protection static |
CTS | Motor stalling relay |
DBAE4 | Rotor earth fault |
DTH | Static transformer percentage biased differential with harmonic restraint |
FMG11 | Over frequency relay |
FMG12 | Under frequency |
GTT | Over fluxing |
HORM4 | Tran slay plain feeder medium speed pilot wire |
TTT | Transformer oil/winding temp indicator with alarm and trip functions |
VAG11 | AC under voltage or over voltage with fixed setting |
VAG21 | AC under voltage or over voltage with fixed setting with drop off pick up ratio |
VAJH13 | Low burden high speed tripping relay with hand reset contact |
VAJ513 | Low burden high speed tripping relay with self reset contact |
VATX11 | High speed tripping relay with electrical or hand and electrical reset contact |
VAT | Independent (definite) time delay relay |
VAX12 | DC supply failure relay |
VAX21 | Trip circuit supervision relay when the circuit breaker is closed |
VAX31 | Trip circuit supervision relay when the circuit breaker is either open or closed. |
VDH12 | Inverse time natural displacement relay for use in distribution system |
VTT | Static definite time delay relay |
YEGF | Generator asynchronous running detection relay |
Wednesday, 18 April 2012
Relay numbering
Subscribe to:
Post Comments (Atom)
SOP, Standard Operating Procedures
1.1 . Definition SOP is termed commonly as Standard Operating Procedures- SOP Characteristics of SOP- 1) Carry out the operati...
-
Winding and weight of induction and submersible motor – winding weight and motor weight Typical motor, 3 Ph, 40 H, 415v Sr. ...
-
Busbar Bus bar A bus bar (also spelled busbar, buss bar or busbar), is a str...
-
TRANSFORMER 11/0.415 KV Sr TR KVA Un tanking Mass (core+ winding), KG Oil Mass, KG Total mas...
Very informative site
ReplyDelete