Transformer: transformers in distribution s, step down the primary voltage to lower values suitable for distribution purpose. Three phase oil cooled in delta/star are used. Sometimes 3-winding transformers are also used so that a different supply voltage may be obtained, from tertiary.
Circuit breakers: whenever a fault occurs, the relays sense the fault and send trip signal to the circuit breaker. The circuit breakers disconnect and isolate the faulty section. Oil circuit breakers, air blast circuit breakers, and sulphur hexafluoride circuit breakers are used in power systems
Isolators: whenever maintenance or repair work is to be carried out on an equipment in a substation , it is disconnected from the supply by isolators. They are normally operated on no load. Isolators are generally interlocked with circuit breakers and earthing switches.
CT/PT: a current transformer steps down the line current for the purpose of relaying and metering. Generally single turn primary current transformers are used. The line or conductor passes through the core and acts as primary. The secondary, having large no. of turns, is wound on the core. The instrument or relay is connected to the secondary. The secondary rated current is either 1A or 5A. Normally 1A is used for metering and 5A is used for protection.
A voltage or potential transformer is used to step down the system voltage to a low value for metering and relaying. It may be an iron core type or capacitive voltage transformer (CVT), the CVT being more commonly used. The rated secondary voltages are 110V or 230V line to line.
Bus bar: the incoming and outgoing circuits are connected to bus bars. These may be either rigid aluminium tubular bus bars supported on post insulators or flexible ACSR stranded conductors bus bars supported from two end by strain insulators.
Protective relays: wherever a fault occurs the protective relay operates and sends a trip signal to circuit breakers. The relays are housed in panel in the control room.
Time graded over current protection is used for feeders. Distance protection and carrier current protection are used for transmission line. Differential protection is used for transformer protection.
Surge arrester: surge arrestor protects the substation equipment from lighting and switching surges. Present day power system invariably uses valve type arrestors.
Earthing switch: the earthing switch is connected between the line conductor and earth and is mounted on the frame of of isolator. Normally it is in open position. When the line is disconnected the earthing switch is closed to discharge the trapped charges to earth.
Station earthing system: the function of station earthing system is to provide a low resistance path for flow of earth fault current for safety of equipment and personnel.
Shunt capacitors: they supply the reactive power to the loads and thus help in improving the power factor. They are switched on during pick load conditions and switched off during opp-peak condition. Shunt capacitor banks are connected in star or delta across the tertiary winding of the transformers.
Station battery and charging current: a substation needs DC supply for protection and control purposes. This supply is obtained from batteries. 110Vdc supply is used for medium size substations while 240V supply is used for large substations. The batteries are equipped with charging equipment.
Typical Limiting Values of Sub Station Electrical Equipments.
1. Transformer / Reactor:
Sr. No.
|
Equipment / test data
|
Permissible limits
|
Reference
|
A)
|
Transformer oil
| ||
a) BDV
| |||
-At the time of first charging
|
600 kV (Gap – 2.5 mm) – Minimum
|
IS – 1866
| |
-During O&M
|
50 kV (Gap – 2.5 mm) – Minimum
|
IS – 1867
| |
b) Moisture content
|
IS – 1868
| ||
-At the time of first charging
|
15 PPM (Max.)
|
IS – 1869
| |
-During O&M
|
25 PPM (Max.)
|
IS – 1870
| |
c) Resistivity at 90 degree C
|
0.1-1012 Ohm-CM (Min.)
|
IS – 1871
| |
d) Acidity
|
0.2 mg KOH/gm (Max.)
|
IS – 1872
| |
e) IFT at 27 degree C
|
0.018 N/M (Min.)
|
IS – 1873
| |
f) Tan delta at 90 degree C
|
0.20 (Max.)
|
IS – 1874
| |
g) Flash point
|
126 Deg. C (Min.)
|
IS – 1875
| |
B)
|
Vibration level for reactors
|
200 Microns (Peak to Peak)
|
IS – 1876
|
60 Microns (Average)
|
IS – 1877
| ||
C)
|
Tan delta for bushing at 20 Deg. C
|
0.007*
|
IEC – 137
|
D)
|
Capacitance for bushing
|
+ 5% variation
|
IEC – 138
|
E)
|
IR value for winding
|
1000 M-Ohm By 5.0/10.0 kV Megger
|
IEC – 139
|
F)
|
Tan delta for windings at 20 Deg. C
|
0.007*
|
IEEE/C57.12.90.1980
|
G)
|
Contact resistance of bushing terminal connectors
|
10 M. Ohm / Connector
|
NGC.UK Recommendations
|
H)
|
Turret Neutral CT ratio errors
|
39
|
IS – 2705
|
2. Circuit Breakers
Sr. No.
|
Equipment / test data
|
Permissible limits
|
Reference
|
A)
|
Dew point of SF6 gas
|
Dew point values as per Annexure – II
| |
B)
|
Dew point of operating air
|
-45 Deg. C at ATM. Pressure
| |
C)
|
CB Operating timings
|
400 kV 220KV
| |
a) Closing time (Max.)
|
150 MS 200MS
| ||
b) Trip time (Max.)
|
25 MS 35MS
| ||
c) Close/trip time, Pole discrepancy
| |||
– Phase to Phase (Max.)
|
3.33 MS 3.33MS
| ||
-Break to break (Max.) of same phase
|
2.5 MS 2.5MS
| ||
D)
|
PIR time
| ||
BHEL make
|
12-16 MS
|
Manufacturers Recommendations
| |
ABB make
|
8-12 MS
|
Manufacturers Recommendations
| |
NGEF make
|
8-12 MS
|
Manufacturers Recommendations
| |
M&G make
|
8-12 MS
|
Manufacturers Recommendations
| |
TELK make
|
8-12 MS
|
Manufacturers Recommendations
| |
ABB make (HVDC)
|
8-12 MS
|
Manufacturers Recommendations
| |
E)
|
PIR opening time prior to opening of main contacts (ABB, CGL, NGEF make CBs)
|
5 MS (Min.) at rated pressure
|
Manufacturers Recommendations
|
F)
|
Pir and main contacts overlap time [BHEL, M&G, ABB (imported) make CBs]
|
6 MS (Min.) at rated pressure
|
Manufacturers Recommendations
|
G)
|
Tan delta of grading capacitors
|
0.007 at 20 Deg. C
| |
H)
|
Capacitance of grading capacitors
|
Within + 10% / -5% of the rated value
|
IEC 359
|
I)
|
Contact resistance of CB
|
150 M. Ohm
| |
J)
|
Contact resistance of CB terminal connector
|
10 M. Ohm per connector
|
NGC, UK recommendations
|
K)
|
IR value:
| ||
1. Phase – earth
|
1000 M Ohm (Min.) by 5.0 / 10.0 kV Megger
| ||
2. Across open contacts
|
1000 M Ohm (Min.) by 5.0/10.0 kV Megger
| ||
3. Control cables
|
50 M Ohm (Min.) by 0.5 kV Megger
| ||
L)
|
Pressure switch settings
| ||
-SF6 gas pressure switches
|
Within + 0.1 Bar of set value
| ||
-Operating air pr. Switches
|
Within + 0.1 Bar of set value
| ||
-Operating oil pr. Switches
|
Within + 0.1 Bar of set value
| ||
M)
|
BDV of oil used for MOCB
| ||
-At the time of filling
|
40 kV at 2.5 mm Gap (Min.)
|
Mfgs. Recommendation
| |
-During O&M
|
20 kV at 2.5 mm Gap. (Min.)
|
Mfgs. Recommendation
|
3. Current Transformer
Sr. No.
|
Equipment / test data
|
Permissible limits
|
Reference
|
A)
|
IR value
| ||
1. Primary – earth
|
1000 M – Ohm (Min.) by 5.0/10.0 kV Megger
| ||
2. Secondary – earth
|
50 M – Ohm (Min.) by 0.5 kV Megger
| ||
3. Control cables
|
50 M-Ohm (Min.) by 0.5 kV Megger
| ||
B)
|
Tan delta value
|
0.007* at 20 Deg. C
| |
C)
|
Terminal Connector
|
10 M-Ohm per connector
|
NGC, UK Recommendations
|
D)
|
CT ratio errors
|
+ 3% -Protection cores
|
IS – 2705
|
D)
|
CT ratio errors
|
+ 1% -Metering cores
|
IS – 2706
|
4. Capacitive Voltage
Sr. No.
|
Equipment / test data
|
Permissible limits
|
Reference
|
A)
|
Tan Delta
|
0.007* at 20 Deg. C
| |
B)
|
Capacitance
|
Within +10%/-5% of the rated value
|
IEC – 358
|
C
|
Contact resistance of terminal connector
|
10 M-Ohm per connector
|
NGC, UK Recommendations
|
D)
|
IR Value
|
IR Value
| |
1. Primary – earth
|
1000 M – Ohm (Min.) by 5.0/10.0 kV Megger
| ||
2. Secondary – earth
|
50 M – Ohm (Min.) by 0.5 kV Megger
| ||
3. Control cables
|
50 M-Ohm (Min.) by 0.5 kV Megger
| ||
E)
|
EMU tank oil parameters
|
EMU tank oil parameters
| |
a) BDV (Min.)
|
30 kV (Gap. –2.5 mm)
|
IS – 1866
| |
b) Moisture content (Max.)
|
35 ppm
|
-do-
| |
c) Resistivity at 90 Deg. C
|
0.1 – 1012 Ohm. – CM
|
-do-
| |
d) Acidity
|
0.5 mg kOH /gm (Max.)
|
-do-
| |
e) IFT at 27 Deg. C
|
0.018 N/M (Min.)
|
-do-
| |
f) Tan delta at 90 Deg. C
|
1.0 Max.
|
-do-
| |
g) Flash point
|
125 Deg. C (Min.)
|
-do-
| |
F)
|
CVT voltage ratio errors
|
+ 5% protection cores
|
IEEE/C93.1.1990
|
F)
|
CVT voltage ratio errors
|
+ 0.5% metering cores
|
IEC 186
|
5. Isolators
Sr. No.
|
Equipment / test data
|
Permissible limits
|
Reference
|
A)
|
Contact resistance
|
300 M-Ohm. (Max.)
| |
B)
|
Contact resistance of terminal connector
|
10 M – Ohm per connector
|
NGC, UK Recommendations
|
C)
|
IR value
| ||
1. Phase – earth
|
1000 M – Ohm (Min.) by 5.0/10.0 kV Megger
|
NGC, UK Recommendations
| |
2. Across open contacts
|
1000 M – Ohm (Min.) by 5.0/10.0 kV Megger
|
NGC, UK Recommendations
| |
3. Control cables
|
50 M-Ohm (Min.) by 0.5 kV Megger
|
6. Surge Arrester
Sr. No.
|
Equipment / test data
|
Permissible limits
|
Reference
|
A)
|
Leakage current
|
500 M-Amp. (Resistive)
|
Hitachi, Japan Recom.
|
B)
|
IR value
|
1000 M-Ohm. (Min.)
|
Hitachi, Japan Recom.
|
7. Miscellaneous
Sr. No.
|
Equipment / test data
|
Permissible limits
|
Reference
|
A)
|
Station earth resistance
|
1.0 Ohm (Max.)
| |
B)
|
Thermo vision scanning
| ||
Temp. up to 15 Deg. C (above ambient)
|
Normal
| ||
Temp. above 15-50 Deg. C (above ambient)
|
Alert
| ||
Temp. above 50 Deg. C (above ambient)
|
To be immediately attended
| ||
C)
|
Terminal connectors – Contact resistance
|
10 M-Ohm per connector
|
HGC, UK Recommendations
|
D)
|
IR values
| ||
1. All electrical motors
|
50 M-Ohm (Min.) by 0.5 kV Megger
| ||
2. Control cables
|
50 M-Ohm (Min) by 0.5 kV Megger
| ||
3. Lt. Transformers
|
100 M.-Ohm (Min.) by Megger
| ||
4. Lt. Switchgears
|
100 M – Ohm (Min.) by 0.5 kV Megger
|
8. Batteries
Sr. No.
|
Equipment / test data
|
Permissible limits
|
Reference
|
A)
|
Terminal connector resistance
|
10 M – Ohm + 20%
|
ANSI/IEEE – 450 1989
|
B)
|
Specific gravity
|
1200 + 5 GM/L at 27 Deg. C
|
Temperature Correction Factor for Tan Delta Measurement
Sr. No.
|
Oil temperature Deg. C
|
Correction factor(K)
|
1
|
10
|
0.8
|
2
|
15
|
0.9
|
3
|
20
|
1.0
|
4
|
25
|
1.12
|
5
|
30
|
1.25
|
6
|
35
|
1.40
|
7
|
40
|
1.55
|
8
|
45
|
1.75
|
9
|
50
|
1.95
|
10
|
55
|
2.18
|
11
|
60
|
2.42
|
12
|
65
|
2.70
|
13
|
70
|
3.00
|
If Tan Delta of bushing/winding/CVT/CT is measured at oil temperature T Deg. C. Then Tan Delta at 20 Deg. C shall be as given below:
Tan Delta at 20 Deg. C = Tan Delta at Temp T Deg. C / Factor K.
Dew Point Limits for SF6 Gas in EHV Circuit Breakers
Sr. No
|
Make of C.B
|
Dew point at rated Pr. Deg. C
|
Corresponding dew point at Atmospheric .Pr.
|
Remarks
|
1
|
BHEL
|
-15
|
-36
|
At the time of commissioning
|
-7
|
-29
|
During O&M
| ||
-5
|
-27
|
Critical
| ||
2
|
M&G
|
–
|
-39
|
At the time of commissioning
|
-32
|
During O&M
| |||
3
|
CGL
|
-15
|
-35
|
At the time of commissioning
|
-10
|
-31
|
During O&M
| ||
4
|
ABB
|
-15
|
-35
|
At the time of commissioning
|
-5
|
-26
|
During O&M
| ||
5
|
NGEF
|
-15
|
-36
|
At the time of commissioning
|
-7
|
-29
|
During O&M
|
Note: Dew point of SF6 gas varies with pressure at which measurement is carried out. So it is to be ensured that if measurement is done at pressure other than atmospheric pressure, it needs to be converted to the atmospheric pressure.
Informative blog indeed about Capacitor Voltage Transformer and its manufacturing process.
ReplyDeletethanks for comments
DeleteHi, nice interesting informative blog. We also manufacture and supply Servo Voltage Stabilizers & Isolation and CVT Transformers.
ReplyDeleteThanks for sharing.
thanks for comment. could you send mail on servo voltage stabilizer to amieclub@gmail.com
DeleteValuable information and excellent design you got here! I would like to thank you for sharing your thoughts into the stuff you post!!
ReplyDeleteSubstation Commissioning
The substations are where the voltages are increased to high values by using step up transformers, and after the transmission, they are again stepped down for distribution.
ReplyDeleteTransformer Manufacturer in India
An Advanced Technological Innovation Has Been Used By Our Team Of Corona Lighting Solution As The Best Change Over Switch Manufacturers In The Market. A Versatile Range Of Products Is Available To Suit All Type Of Needs. The Latest Advancements And Continuous Modifications Have Encouraged Us To Provide Our Customers With The Best Quality Switch.
ReplyDeleteYou may also visit: Sheet Metal Boxes Manufacturers
Rashtriya Electrical And Engineering Corporation is a one of the growing name in the area of Air Break Switch Manufacturers in India. We are manufacturing Air Break Switch in Noida and we supply our product pan India. We have a well experience team who make our products by using a best quality of material and latest technology. If you want to know more about our business so contact us or visit our website.
ReplyDeleteGreat post.Thanks for sharing.
ReplyDeleteJost’s Battery ground Fault Test Equipment
provides innovative solutions for internal material handling needs for its customers so that it improves the efficiencies of their processes.